Plan Review Notes
Plan Review Notes For Permit 07090828
Permit Number 07090828
Review Stop B
Sequence Number 1
Notes
Date Text
2007-10-30 14:37:11 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $ 3.44 FOR STATE
 RADON FEES THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO
 FURTHER PLAN REVIEW
  
 4) SUBMIT ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 5)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG ******NOTE
 THAT ONLY ONE COPY OF PRODUCT APPROVAL WAS SUBMITTED
 FOR DOORS, WINDOWS AND SEVERAL OF THE SIMPSON TIE
 CONNECTORS******
  
 6)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
 ******NOTE THE DOOR AND WINDOW PRODUCT APPROVALS WERE
 NOT REVIEWED AND APPROVED******
  
 7)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
 ******NOTE THE DOOR AND WINDOW PRODUCT APPROVALS DO NOT
 CONTAIN THE STATE APPROVAL SHEETS, PLEASE SEE THAT THE
 CORRECT FL# IS WRITTEN AT THE TOP OF THE NOA******
  
 8)PRODUCT APPROVALS THAT WERE SUBMITTED FOR LINTELS
 ARE FROM THE 2001 CODE CYCLE AND THE MIAMI-DADE
 EVALUATION REPORT(NOA) HAS EXPIRED. ALSO THE SHINGLES,
 USING THE STATE APPROVAL ARE VALIDATED BY UL AND ARE
 APPROVED ONLY TO 110 MPH. IF THESE SHINGLES ARE TO BE
 USED PROVIDE 2 COPIES OF THE UPDATED MIAMI-DADE REPORT
 FOR USE AS A LOCALLY APPROVED PRODUCT. PLEASE NOTE THAT
 MIAMI-DADE THAT WAS SUBMITTED HAS EXPIRED.
  
 THE FOLLOWING COMMENTS PERTAIN TO THE TRUSS
 ENGINEERING:
  
 9)A DESIGN PROFESSIONAL THAT IS REGISTERED TO
 PRACTICE UNDER CHAPTER 481 OR 471 OF THE FLORIDA
 STATUTES SHALL AFFIX THEIR OFFICIAL SEAL, SIGNATURE AND
 DATE TO SAID DRAWINGS AND SPECIFICATIONS PER 106.1 FBC
 2004.
  
 10)ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME,
 ADDRESS, AND LICENSE NUMBER ON EACH SHEET THAT BEARS
 THEIR SEAL PER
 61G15-23.002(2) FAC
  
 ******PLEASE NOTE THAT THE GENERIC NOTES AND DRAWINGS
 WILL BE ACCEPTABLE IF TWO COPIES OF AN INDEX SHEET THAT
 MEETS THE REQUIREMENTS OF NOTES 9 & 10 ARE MET******
  
 11)REMOVE ALL EXPIRED AND INVALID PRODUCT APPROVALS
 FROM FURTHER RESUBMITTALS AND REMOVE ALL OLD PAGES AND
 RESUBMIT 2 COMPLETE SETS OF NEW DRAWINGS AND INCLUDE 1
 COPY OF THE OLD PAGES ONLY FOR REFERENCE
  
 12)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 BLDG PLAN REVIEW