Plan Review Notes
Plan Review Notes For Permit 07090797
Permit Number 07090797
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-23 15:41:16DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA
 ACCESSIBILITY CODE.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS:
  
 1. THE RESUBMITTED PLANS DO NOT REFLECT EVERYTHING ON
 THE PERMIT APPLCATION. PERMIT APPLICATION STATES
 "REMOVE & INSTALL JACUZZI TUB WITH FIXTURES". THE
 RESUBMITTED PLANS DO NOT INDICATE THIS WORK BEING DONE.
 PER FBC-2004 CHAPTER 1, SECTION 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 2. THE RESUBMITTED SANITARY ISOMETRIC RISER DIAGRAMS
 ARE INDICATING A WASTE STACK FOR A 2ND FLOOR WASHING
 MACHINE BOX. THE PERMIT APPLICATION DOES NOT INDICATE
 THIS WORK BEING DONE.
 NOTE: THE PERMIT APPLICATION STATES "DESCRIBE PROJECT
 IN DETAIL (FAILURE TO DO SO MAY RESULT IN DELAYS). PER
 FBC-2004 CHAPTER 1 SECTION 105 PERMITS, AND 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 3. FBC-2004 CHAPTER 1,SECTION 106.3.4.3:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
 NOTE: THE RESUBMITTED FLOOR PLAN DRAWINGS ARE NOT
 COMPLIANT.
  
 4. PER FC 713.13 (1) THRU (6): A NOTICE OF
 COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY
 COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE
 HWY., BEFORE A PERMIT CAN BE ISSUED.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]