| Plan Review Notes For Permit 07090792 |
| Permit Number |
07090792 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-23 14:02:55 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | | | | 1.CHANGES TO THE PLAN ARE TO BE DONE BY THE ARCHITECT | | | OR ENGINEER SEALING THE PLAN.IT APPEARS THAT THE | | | ARCHITECT HAS REVISED THE ENGINEER'S PLAN.AS ONE | | | CHANGE MAKES THE REVISED PLAN LESS CONSERVATIVE (OTHER | | | CHANGES TO THE SIZE MADE THE AWNINGS SMALLER WITH ONE | | | EXCEPTION, WHICH INCREASED THE SIZE OF THE AWNING), | | | THIS MUST BE APPROVED BY THE AWNING ENGINEER. | | | | | | 2.SHEET 1, ENGINEERING EXPRESS NOTE 8 STATES DESIGN | | | CRITERIA AS ASCE7-98; THIS SHOULD BE ASCE7-02 FBC | | | CHAPTER 35. | | | | | | 3.IT IS NOT CLEAR IF ADDING A SIDE VALANCE AFFECTS | | | THE ENGINEERING.HAVE THE ENGINEER REVISE THE PLAN TO | | | INCLUDE THE CHANGES REQUESTED BY THE ARCHITECT. | | | | | | 4.THE ENGINEER SPECIFIES 48" MINIMUM HEIGHT; DOES HE | | | MEAN MAXIMUM?PLEASE ADDRESS BY REVISING THE NOTE OR, | | | IF IT IS INDEED A MINIMUM SIZE, REVISE THE ENGINEERING | | | AS THE ARCHITECT IS SPECIFYING AWNINGS WHICH ARE LESS | | | THAN 48" IN HEIGHT. | | | |
|