Plan Review Notes
Plan Review Notes For Permit 07090784
Permit Number 07090784
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-11 08:44:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED TO SHOW THE SIZE OF THE RETURN AIR TRANSFER
 DUCT (FLEX), SEE 2004 FBC/M 601.4.
  
 2) NEED TO PROVIDE SUPPLY AIR TO OFFICE, SEE 2004 FBC/M
 401.2.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]


Account Summary | Usage Policy | Privacy Policy