| Date |
Text |
| 2007-10-20 10:28:48 | |
| | PLANS WERE NOT SENT TO ELECTRICAL SFR UNTIL 10/19 |
| 2007-10-20 10:24:10 | 2007-10-20 10:24:10 |
| | |
| | ** DENIED ** |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE EACH BLDG IS SHOWING AN ELECTRICAL |
| | RISER OF A SEPARATE ELECTRICAL SERVICE WHICH IS NOT |
| | PERMITTED. 230.2. |
| | PLEASE SEE THAT THE PANEL SCHEDULES AS SUBMITTED ON |
| | EACH DO NOT ACCURATELY REFLECT ANY OF THE ELECTRICAL ON |
| | PLANS. |
| | |
| | 3) NOTE: PLEASE SEE 225.31-225.39 AS SEPARATE |
| | SUB-PANELS AT EACH BUILD FED FROM THE MAIN HOUSE WOULD |
| | BE REQUIRED. THIS IS ONLY BASED ON USE AND PERMITTED |
| | USE FROM ZONING AND OTHER TRADES. |
| | AS NONE IS SHOWN, REVIEW CAN NOT BE DONE. (LOCATION, |
| | SIZE, OVER CURRENT PROTECTION, ETC) |
| | PLEASE SEE 240.4, 310.16 AND 408.4 FOR REQUIRED PANEL |
| | SCHEDULE(S) ETC |
| | FBC 106.3.5.4, 106.1.2 |
| | |
| | 4) NOTE: PLEASE SEE 250.32 AND 250.50 FOR GROUNDING |
| | ELECTRODE SYSTEM REQUIRED AT EACH STRUCTURE. |
| | THIS WILL INCLUDE GROUNDING FROM THE PANELS/DISCONNECTS |
| | FROM NOTE #3 ABOVE TO FOOTER STEEL, AND ANY METAL COLD |
| | WATER PIPE. |
| | THESE ARE THE *MINIMUM* THAT ARE REQUIRED. |
| | |
| | 5) NOTE: PLEASE SEE MISSING BATH ROOM REQUIRED |
| | DEDICATED CIRCUIT(S) PER 210.52D, 210.8A2, 210.11C3. |
| | MUST BE 20AMP AND #12. |
| | THEREARE NONE SHOWN ON PLANS, AND AS NEW PANELS FOR |
| | EACH BUILDING WILL BE REQUIRED, NO REVIEW CAN BE DONE |
| | OF THESE. |
| | |
| | 6) NOTE: PLEASE SEE MISSING SMOKE ALARMS PER NFPA-72 |
| | 11.5.1.1.1, 11.8.3 |
| | MUST BE INSTALLED AS THESE ARE CLEARLY ADAPTABLE |
| | SLEEPING ROOMS/APARTMENTS. |
| | PLEASE SEE THE NEXT COMMENT ALSO FOR 210.12. |
| | |
| | 7) NOTE: PLEASE SEE AS THE PLANS APPEAR TO SHOW AND |
| | LEND TO APARTMENT USE AND THE FACT THAT THESE ROOMS ARE |
| | ADAPTABLE SLEEPING ROOMS, ARC FAULT PROTECTION WILL BE |
| | REQUIRED PER 210.12 |
| | |
| | 8) NOTE: PLEASE SEE THAT NO WHITE-OUT OF ANY KIND MAY |
| | BE PLACED ON PLANS. |
| | FS 481, FBC 106.1 |
| | |
| | 9) NOTE: PLEASE SEE PLUMB PLANS INDICATE TWO SINKS, |
| | HOWEVER ONLY ONE IS SHOWN ON PLANS. THIS WILL DIRECTLY |
| | AFFECT THE ELECTRICAL REQUIREMENTS IF A KITCHEN IS |
| | BEING INSTALLED OR WIRED ON-SITE. A FIELD INSPECTION OF |
| | ELECTRICAL SYSTEMS OF WHICH MAY ALREADY BE WIRED ETC |
| | MAY BE DONE TO ACCURATELY COME UP WITH WHAT WORK IS |
| | DONE, TO BE DONE, USE ETC. |
| | PLANS DO NOT CORRELATE FOR USE. |
| | ARCHITECT TO SEE FS 481 FOR DESIGN RESPONSIBILITY. |
| | PLANS MAY BE RETAINED BY THIS OFFICE AND PLACED WITH |
| | OTHER PLANS RETAINED IN FILE FOR THIS DESIGNER. PLANS |
| | ARE REQUIRED TO BE DESIGNED FOR ACCURATE USE, AND THE |
| | MINIMUM CODE(S). |
| | |
| | 10) NOTE: PLEASE SEE AS PLANS INDICATE A WATER HEATER |
| | WITH WHITE OUT OVER IT, PLEASE INCLUDE ON PLANS IF SO |
| | INSTALLED OR PROPOSED. |
| | PLEASE SEE 422.17 AS THE WATER HEATER MAY NOT BE IN A |
| | CLOSET. |
| | |
| | 11) NOTE: PLEASE SEE DEPENDING ON USE; PLEASE SEE ALL |
| | OF 210.52 WHICH SEVERAL ITEMS MAY BE REQUIRED. |
| | |
| | ** PLEASE KNOW PLANS ARE REQUIRED TO BE DESIGNED TO |
| | *MINIMUM* STANDARDS FOR CODE COMPLIANCE FOR USE AND IT |
| | IS THE RESPONSIBILITY OF ALL PERSONS INVOLVED. |
| | |
| | ** PLEASE KNOW AS THERE ARE NUMEROUS ITEMS NOT YET |
| | SHOWN OR SUBMITTED UNDER THE DESIGN, THERE MAY BE NEW |
| | COMMENTS ON THE FOLLOWING REVIEW WHICH CAN NOT BE MADE |
| | AT THIS TIME. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |