| | DENIED |
| | |
| | 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL |
| | COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006 |
| | AMENDMENTS PER 106.1.1 FBC* |
| | |
| | 2)PROVIDE THE WIND DESIGN DATA THAT APPLIES TO |
| | BUILDING PER 1603.1.4 FBC |
| | |
| | 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS |
| | LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS |
| | AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST |
| | EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC |
| | (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES |
| | PER 108.3 FBC* |
| | |
| | 4)IF THE ACCESSORY BUILDINGS ARE DEEMED TO BE LIVING |
| | SPACES THE STATE OF FLORIDA REQUIRES COLLECTION OF A |
| | RADON SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON |
| | UNDER ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL |
| | BE ADDED TO THE PERMIT APPLICATION FEES. |
| | |
| | NOTE: FEES ARE DUE IN THE AMOUNT OF $785.96FOR |
| | INCREASED VALUE THIS AMOUNT IS REQUIRED TO BE PAID |
| | PRIOR TO FURTHER PLAN REVIEW. THESE FEES ARE FOR |
| | UTILITY BUILDINGS AND AS ABOVE IF DEEMED RESIDENCE |
| | USAGE THE FEES WILL BE INCREASED. |
| | |
| | 5)PROVIDE DRAWINGS AND SPECIFICATIONS THAT ARE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION,NATURE, AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1 |
| | FBC* PLEASE NOTE THAT PERMIT APPLICATION STOP WORK |
| | ORDER AND NOTICE OF VIOLATION ALL INDICATE THAT |
| | BUILDINGS ARE OF CBS CONSTRUCTION. |
| | |
| | 6)IF BUILDINGS ARE RESIDENCESTWO COPIES OF ENERGY |
| | CALC'S PER 13-101.2.2 FBC. BE SURE THAT THEY ARE SIGNED |
| | AND DATED BY PREPARER AND OWNER/AGENT PRIOR TO |
| | SUBMITTAL |
| | |
| | 7)PROVIDE SCHEDULE FOR PRECAST LINTEL THAT WILL BE |
| | USED AND OPENING SIZES TO COMPLY WITH 2104.1.5 FBC FOR |
| | MIN BEARING |
| | |
| | 8)DRAWINGS SHALL SHOW THE MINIMUM DEPTH OF FOUNDATION |
| | ON THE WALL SECTIONS PER R403.1.4 FBC RES. |
| | |
| | 9)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF |
| | EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE |
| | SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES. |
| | ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG |
| | |
| | 10)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE |
| | 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC* |
| | |
| | 11)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA |
| | STATE PRODUCT APPROVAL COVER |
| | SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON |
| | WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT |
| | SUBMITTED APPLICATIONS WILL BE DENIED |
| | |
| | 12) NO PRODUCT APPROVALS WERE SUBMITTED FOR LINTELS, |
| | CONNECTORS AND STRAPS, WINDOWS, DOORS AND ROOFING |
| | MATERIAL, IN LUE OF PRODUCT APPROVALS STRAPS/CONNECTORS |
| | MAY BE LISTED IN A SCHEDULE ON THE DRAWINGS COMPLETE |
| | WITH THE STATEWIDE PRODUCT APPROVAL NUMBERS OR SUBMIT |
| | SIMPSON TIE?S COMPLETE FLORIDA INDEX WITH CONNECTORS TO |
| | BE USED HIGHLIGHTED |
| | |
| | 13)PROVIDE 2 COMPLETE SETS OF ALL DRAWINGS AND |
| | SUBMITTALS |
| | |
| | 14)A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT IS REQUIRED PRIOR TO |
| | A PERMIT BEING ISSUED |
| | |
| | 15)ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING, |
| | ELECTRICAL AND MECHANICAL AND ROOFING |
| | |
| | 16)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS |
| | OF NEW DRAWINGS AND INCLUDE 1 COPY OF THE OLD PAGES |
| | ONLY FOR REFERENCE |
| | |
| | 17)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, |
| | IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE |
| | ACTUAL PERMIT SETS OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE |
| | PERMIT APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | 18)UNTIL INSPECTION OF THE INTERIOR OF THESE |
| | BUILDINGS IS UNDERTAKEN AND PLANS CAN BE VERIFIED TO BE |
| | TRUE, A COMPLETE PLAN REVIEW CANNOT BE MADE AND MORE |
| | COMMENTS MAY BE FORTHCOMING. FOR ANINSPECTION OF |