Plan Review Notes
Plan Review Notes For Permit 07090773
Permit Number 07090773
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-12 08:54:07*****UNSAT*****
  
  
 1.THE SUITE NUMBER SHALL BE INCLUDED WITH THE ADDRESS
 LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 4.ON SHEET E-3, THERE IS AN EXISTING EXIT LIGHT IN
 THE NORTH END OF THE MAIN CORRIDOR THAT DIRECTS
 PERSON(S) TO EITHER DIRECTION FOR EXITING.WHERE IS
 THE MEANS OF EGRESS GOING NORTH?
  
 5.ON SHEET E-3,THERE IS AN EXISTING EXIT LIGHT AT
 THE EASTERN MOST END OF A CORRIDOR. PLEASE INDICATE
 WHERE THIS EXIT LIGHT IS DIRECTING PERSON(S) TO EXIT.
  
 6.SHOW LOCATION OF THE EMERGENCY LIGHTS FOR THIS
 TENANT SPACE.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722


Account Summary | Usage Policy | Privacy Policy