| 2007-10-05 11:49:35 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} 645.10 DISCONNECTING MEANS |
| | A MEANS SHALL BE PROVIDED TO DISCONNECT POWER TO ALL |
| | ELECTRONIC EQUIPMENT IN THE INFORMATION TECHNOLOGY |
| | EQUIPMENT ROOM. THERE SHALL ALSO BE A SIMILAR MEANS TO |
| | DISCONNECT THE POWER TO ALL DEDICATED HVAC SYSTEMS |
| | SERVING THE ROOM AND CAUSE ALL REQUIRED FIRE/SMOKE |
| | DAMPERS TO CLOSE. THE CONTROL FOR THESE DISCONNECTING |
| | MEANS SHALL BE GROUPED AND IDENTIFIED AND SHALL BE |
| | READILY ACCESSIBLE AT THE PRINCIPAL EXIT DOORS. THE UPS |
| | DISCONNECT DOES NOT COMPLY WITH THIS ARTICLE. SHEET |
| | E-2. |
| | |
| | 2} 645.4(3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS |
| | INSTALLED. PROVIDE THE LISTING AND MANUFACTURERS |
| | SPECIFICATIONS FOR THE UPS SHOWN ON SHEET E-2. |
| | |
| | 3} 645.4 (5) THE ROOM IS SEPARATED FROM OTHER |
| | OCCUPANCIES BY FIRE-RESISTANT-RATED WALLS, FLOORS, AND |
| | CEILINGS WITH PROTECTED OPENINGS. PROVIDE DETAILS |
| | INDICATING COMPLIANCE WITH THIS ARTICLE. |
| | |
| | 4} SHEET E-4 INDICATES THE FEED TO THE IT PANEL BEING |
| | 4-#3/0, WITH A #8 EQUIPMENT GROUND. THE PANEL IS LISTED |
| | AS SINGLE PHASE THREE WIRE. CORRELATE THE FEED |
| | CONDUCTORSWITH THE PANEL RATING. |
| | |
| | 5} THE EQUIPMENT GROUNDING CONDUCTOR RAN WITH THE |
| | FEEDER TO THE IT PANEL,MUST COMPLY WITH 250.122, |
| | MINIMUM #6. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |