2007-10-05 11:49:35 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
 ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} 645.10 DISCONNECTING MEANS
 A MEANS SHALL BE PROVIDED TO DISCONNECT POWER TO ALL
 ELECTRONIC EQUIPMENT IN THE INFORMATION TECHNOLOGY
 EQUIPMENT ROOM. THERE SHALL ALSO BE A SIMILAR MEANS TO
 DISCONNECT THE POWER TO ALL DEDICATED HVAC SYSTEMS
 SERVING THE ROOM AND CAUSE ALL REQUIRED FIRE/SMOKE
 DAMPERS TO CLOSE. THE CONTROL FOR THESE DISCONNECTING
 MEANS SHALL BE GROUPED AND IDENTIFIED AND SHALL BE
 READILY ACCESSIBLE AT THE PRINCIPAL EXIT DOORS. THE UPS
 DISCONNECT DOES NOT COMPLY WITH THIS ARTICLE. SHEET
 E-2.
  
 2} 645.4(3) LISTED INFORMATION TECHNOLOGY EQUIPMENT IS
 INSTALLED. PROVIDE THE LISTING AND MANUFACTURERS
 SPECIFICATIONS FOR THE UPS SHOWN ON SHEET E-2.
  
 3} 645.4 (5) THE ROOM IS SEPARATED FROM OTHER
 OCCUPANCIES BY FIRE-RESISTANT-RATED WALLS, FLOORS, AND
 CEILINGS WITH PROTECTED OPENINGS. PROVIDE DETAILS
 INDICATING COMPLIANCE WITH THIS ARTICLE.
  
 4} SHEET E-4 INDICATES THE FEED TO THE IT PANEL BEING
 4-#3/0, WITH A #8 EQUIPMENT GROUND. THE PANEL IS LISTED
 AS SINGLE PHASE THREE WIRE. CORRELATE THE FEED
 CONDUCTORSWITH THE PANEL RATING.
  
 5} THE EQUIPMENT GROUNDING CONDUCTOR RAN WITH THE
 FEEDER TO THE IT PANEL,MUST COMPLY WITH 250.122,
 MINIMUM #6.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  