2007-11-08 07:55:53****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 5.FOR THE CALCULATIONS, ALL INFORMATION REQUIRED BY
 FAC61G15-23.002 IS REQUIRED AND EITHER EACH SHEET IS TO
 BE SIGNED, SEALED, AND DATED OR AN INDEX SHEET IN
 COMPLIANCE WITH FAC61G15-23 IS TO BE USED.
  
 2ND REVIEW, NOT ADDRESSED.PLEASE CONTACT ME IF YOU
 NEED ASSISTANCE.
  
 7.THE SECOND SHEET, THIRD SHEET, AND OTHER SHEETS
 HAVE "#VALUE!" IN A BOX WHERE THERE SHOULD BE A NUMBER.
 THIS APPEARS TO BE AN ERROR MESSAGE GENERATED BY THE
 SOFTWARE.EITHER PREPARE CALCULATIONS WITHOUT THESE
 ERROR MESSAGES OR INCLUDE A LETTER CLARIFYING WHY THIS
 A PART OF THE CALCULATIONS, WHAT THIS MEANS, AND
 RELEVANCE TO THIS JOB.
  
 2ND REVIEW; ENGINEER WROTE A LETTER STATING THAT THIS
 IS AN EXCEL SIZE OF CELL ERROR.I DO NOT BELIEVE THIS
 IS CORRECT; THIS ERROR OCCURS WHEN THERE IS AN
 INCOMPATIBILITY OF FORMAT TYPES, USUALLY INCLUDING A
 TEXT FORMATTED CELL IN THE FORMULA.THIS CAN BE FIXED
 BY REVISING THE FORMULA.PLEASE CONTACT ME IF YOU NEED
 ASSISTANCE.ALSO, EVEN IF IT IS A SIZE ERROR, THIS
 COULD BE CORRECTED BY FORMATTING TO INCLUDE LESS
 NUMBERS AFTER THE DECIMAL AS THIS FIELD SHOULD BE IN
 THE SAME NUMBER RANGE AS THE OTHER NUMBERS (THEREFORE,
 SHOULD FIT THE CELL).