| Plan Review Notes For Permit 07090768 |
| Permit Number |
07090768 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-12-05 15:02:07 | DENIED; | | | 1. SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN . | | | FLOOR PLAN SHOWS 1 LAVATORY AND A TUB. SANITARY RISER | | | DIAGRAM SHOW 2-LAVATORYS AND A SHOWER. | | | 2. TRAP SIZES ARE NOT CORRECT. SEE FBC PLUMBINGTABLE | | | 709.1. BATHTUB TRAP TO BE 1 1/2" AND THE AUTOMATIC | | | CLOTHES WASHER TRAP TO BE 2". | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|