Plan Review Notes
Plan Review Notes For Permit 07090768
Permit Number 07090768
Review Stop P
Sequence Number 2
Notes
Date Text
2007-12-05 15:02:07DENIED;
 1. SANITARY RISER DIAGRAM DOES NOT MATCH FLOOR PLAN .
 FLOOR PLAN SHOWS 1 LAVATORY AND A TUB. SANITARY RISER
 DIAGRAM SHOW 2-LAVATORYS AND A SHOWER.
 2. TRAP SIZES ARE NOT CORRECT. SEE FBC PLUMBINGTABLE
 709.1. BATHTUB TRAP TO BE 1 1/2" AND THE AUTOMATIC
 CLOTHES WASHER TRAP TO BE 2".
 PLUMBING PLAN REVIEW BY;