| Plan Review Notes For Permit 07090768 |
| Permit Number |
07090768 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-16 08:41:34 | | | | | | | | | | APPLICATION #07090768 | | | ELECTRICAL PLAN REVIEW | | | 416 55TH STREET | | | 11/16/07 | | | WEST PALM BEACH, FL. | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND | | | FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE | | | NOTED. | | | | | | 1} THE DISCONNECT SHOWN ON THE RISER(S) DOES NOT | | | INDICATE A RATING. LABEL THE DISCONNECT WITH THE | | | AMPERAGE RATING INTENDED. 215.5 | | | | | | 2} PROVIDE THE AIC RATING FOR THE SERVICE EQUIPMENT | | | PER110.9-110.10. | | | | | | 3} CIRCUIT #6 IN THE ?NEW? PANEL MUST BE ARC FAULT | | | PROTECTED PER 210.12. INDICATE THE SAME ON THE | | | SCHEDULE. THE NUMBERING/NOTE SYSTEM IS SUFFICIENT. | | | | | | 4} NOTE #4 IN THE ?GENERAL ELECTRICAL NOTES? SHOULD | | | INCLUDE A REFERENCE TO 250.52(A)(3), FOOTER STEEL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] | | | |
|