 APPLICATION #07090768
 ELECTRICAL PLAN REVIEW
 416 55TH STREET
 11/16/07
 WEST PALM BEACH, FL.
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND
 FOUND NONCOMPLIANT WITH THE FOLLOWING:
 ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE
 NOTED.
  
 1} THE DISCONNECT SHOWN ON THE RISER(S) DOES NOT
 INDICATE A RATING. LABEL THE DISCONNECT WITH THE
 AMPERAGE RATING INTENDED. 215.5
  
 2} PROVIDE THE AIC RATING FOR THE SERVICE EQUIPMENT
 PER110.9-110.10.
  
 3} CIRCUIT #6 IN THE ?NEW? PANEL MUST BE ARC FAULT
 PROTECTED PER 210.12. INDICATE THE SAME ON THE
 SCHEDULE. THE NUMBERING/NOTE SYSTEM IS SUFFICIENT.
  
 4} NOTE #4 IN THE ?GENERAL ELECTRICAL NOTES? SHOULD
 INCLUDE A REFERENCE TO 250.52(A)(3), FOOTER STEEL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  