2007-10-22 10:00:31DENIED;
 1. THE PERSON TAKING RESPONSIBITY FOR THE DRAWING MUST
 SIGNEACH PAGE.
 2. SEE PLUMBING RISER DIAGRAM PAGE A-4;
 A) AUTOMATIC CLOTHES WASHER BRANCH DRAIN TO
 BE 3" SEE FBC PLUMBING SECTION 406.3.
 B) THE L-SINK SHALL DISCHARGE ABOVE THE W/M
 BRANCH. SECTION 706.3
 3. THE ADDRESS OF JOB SHOULD BE ON EACH PAGE OF THE
 PLANS.
 PLUMBING PLAN REVIEW BY;