| | APPLICATION #07090768 |
| | ELECTRICAL PLAN REVIEW |
| | 416 55TH STREET |
| | |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE, AN AIC RATING. |
| | |
| | 2} LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, METER |
| | ENCLOSURE, DISCONNECTS AND PANELS, SO THAT COMPLIANCE |
| | WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | |
| | 3} PROVIDE LOAD CALCULATIONS PER ARTICLE 220 PART III, |
| | STANDARD OR PART IV OPTIONAL, INDICATE METHOD USED. SEE |
| | 220.83(B) SINCE A/C IS BEING ADDED. |
| | |
| | 4} SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14, RECEPTACLE PER 210.63, LIGHT PER |
| | 210.70(A) (3), FOR THE AHU IN THE ATTIC. |
| | |
| | 5} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| | 250.66, #2 FOR 4/0 SERVICE CONDUCTORS. |
| | |
| | 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| | FS, RESPECTIVELY. THE CONTRACTOR OF RECORD MAY BE THE |
| | DESIGN PROFESSIONAL IF EXEMPTIONS UNDER CHAPTER |
| | 471.003, FLORIDA STATUTES, IF EXEMPTIONS APPLY. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |