| 2007-10-24 16:42:11 | 2004 FBC W/2007 REVISIONS |
| | LEVEL 2 ADDITION |
| | |
| | DENIED BY BUILDING |
| | |
| | 1)SUBMIT A COPY OF THE PAID RECEIPT FOR THE COUNTY |
| | IMPACT FEES. |
| | |
| | 2) SHOW COMPLIANCE WITH R302.1, WHICH REQUIRES EXTERIOR |
| | WALLS TO BE SEPARATED BY 6 FEET OR HAVE WALLS THAT ARE |
| | ONE HOUR FIRE RATED WITH NO OPENINGS. THE SURVEY SHOWS |
| | 5.1' TO THE PROPERTY LINE ON ONE SIDE OF THE ADDITION. |
| | PROVIDE A SITE PLAN THAT SPECIFIES THAT THE DISTANCE TO |
| | ANY STRUCTURES ON THE ADJACENT LOT IS 6 FEET OR MORE. |
| | |
| | 3) THE EXISTING BEDROOM THAT IS HAVING THE WINDOW |
| | ENCLOSED FOR THE ADDITION IS REQUIRED TO MAINTAIN THE |
| | EXISTING LEVEL OF EMERGENCY EGRESS. FBC R 310 AND |
| | EXISTING BUILDING 901.2. |
| | |
| | 4)THE ATTIC ACCESS REQUIRED BY R 807.1, IS SHOWN ON |
| | SHEET A-4 AND THE MECHANICAL PLANS IN THE WRONG |
| | ORIENTATION IN REGARD TO THE ROOF TRUSSES. PLEASE |
| | CORRECT. |
| | |
| | 5) SHOW COMPLIANCE WITH R 320.1. SPECIFY THE TERMITE |
| | TREATMENT THAT WILL BE USED ON THE PLANS. |
| | |
| | 6) SHOW COMPLIANCE WITH R 408.1 AND R 408.3 FOR CRAWL |
| | SPACE VENTILATION AND ACCESS TO UNDER-FLOOR SPACE. |
| | |
| | 7) THE OVERHANG AT THE EAVES IS NOT SPECIFIED ON |
| | SECTION A ON A-3 BUT APPEARS TO BE LESS THAN 6 INCHES. |
| | SHOW COMPLIANCE WITH R320.7, WHICH REQUIRES GUTTERS |
| | WITH DOWNSPOUTS THAT DISCHARGE AT LEAST ONE FOOT AWAY |
| | FROM THE STRUCTURE SIDEWALL. |
| | |
| | 8)SPECIFY ON THE PLANS HOW FBC R806.1 ROOF |
| | VENTILATION IS BEING COMPLIED WITH. |
| | |
| | 9) THE MASONRY AND STEEL NOTES ON A-2 REFERENCE OLDER |
| | EDITIONS OF ACI 530, TMS 402 AND ASCE 5. PLEASE UPDATE |
| | TO THE EDITIONS THAT ARE REFERENCED IN CHAPTER 24 OF |
| | THE 2004 FBC RESIDENTIAL CODE, WHICH ARE ACI 530-05, |
| | TMS 402-02 AND ASCE5-02. |
| | |
| | 10) ON SECTION A 0N SHEET A-3 THE MINIMUM EMBED DEPTH |
| | FOR THE 10" WEDGE ANCHORS USED TO ATTACH THE WALL |
| | LEDGER FOR THE FLOOR SYSTEM IS PRINTED OVER AND |
| | ILLEGIBLE. PLEASE CORRECT. |
| | |
| | 11) SPECIFY THE REQUIRED TRUSS DESIGN LOADS ON THE |
| | PLANS. SEE R802.1.6.1. |
| | |
| | 12) THE TRUSS LAYOUT DRAWING IS REQUIRED TO BE SIGNED, |
| | SEALED AND DATED BY THE TRUSS ENGINEER. SEE R 802.1.6.2 |
| | AND FS 471. |
| | |
| | 13) THE TRUSS LAYOUT DRAWING SHOULD BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | CONFORMANCE TO THE STRUCTURES DESIGN. |
| | |
| | 14) THE MINIMUM LIVE LOAD REQUIRED FOR THE ROOF TRUSS |
| | BOTTOM CORD IS 10 PSF PER TABLE R 301.5. PLEASE CORRECT |
| | TRUSS DRAWING AND LAYOUT DESIGN DATA. |
| | |
| | 15) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY |
| | CALCULATIONS PER FBC CHAPTER 13. |
| | |
| | 16) THE MINIMUM INSULATION REQUIRED ON CONCRETE BLOCK |
| | WALLS BY THE PRESCRIPTIVE REQUIREMENTS OF ENERGY CALC. |
| | FORM 600C-04R IS R-5. ON SECTION A ON A-3, R4-2 |
| | INSULATION IS SPECIFIED ON SECTION A ON A-3. |
| | |
| | 17) THE GEOTECHNICAL SOIL REPORT FROM THE ENGINEER IS |
| | REQUIRED TO BE SIGNED, SEALED AND DATED. FS 471 |
| | |
| | 18) FBC 106.3* CITY AMENDMENTS PRODUCT |
| | APPROVALS. THOSE PRODUCT WHICH ARE |
| | REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| | FOR JURISDICTIONAL APPROVAL. |
| | |
| | 19) THE NOA FOR THE STORM PANELS HAS BEEN REVISED BY |
| | NOA NO. 05-0926.02 AND THE WRONG STATE COVERSHEET WAS |
| | SUBMITTED. THE CORRECT ONE IS FL # 7226. PLEASE |
| | CORRECT. |
| | |
| | 20) PLEASE SUBMIT AN INSTALLATION SCHEDULE INDICATING |
| | THE TYPE OF MOUNT, ANCHOR TYPE, ANCHOR SPACING, EDGE |
| | DISTANCE, GLASS SEPARATION, SPANS, ETC. THE APPROPRIATE |
| | INFORMATION CAN BE CIRCLED ON THE PRODUCT APPROVAL. FBC |
| | 106.1.2 |
| | |
| | 21) THE WRONG COVERSHEET WAS SUBMITTED FOR THE RIDGE |
| | VENT. FL# 243 IS THE ONE THAT CORRESPONDS WITH NOA NO |
| | 07-0125.01 |
| | |
| | 22) PLEASE DO NOT STAPLE THE PRODUCT APPROVALS TO THE |
| | PLANS. SUBMITTING A RESPONSE LETTER STATINGHOW THE |
| | COMMENTS WERE ADDRESSED WILL HELP CUT DOWN PLAN REVIEW |
| | TIME. THANKS. |
| | |