| 2008-04-03 18:47:35 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.SEE ELECTRICAL AND MECHANICAL COMMENTS REGARDING |
| | ENERGY CALCS.CODE COMPLIANT ENERGY CALCS ARE REQUIRED |
| | PRIOR TO PERMIT ISSUANCE AND CANNOT BE PROVISO'D AS |
| | FLORIDA STATUTORY ITEMS CANNOT BE PROVISO ITEMS. |
| | |
| | 2.SEE THE SUBMITTED ENERGY CALCS.NO DOORS ARE |
| | SHOWN.TWO WINDOWS ARE SHOWN, BUT THE PLAN SHOWS MORE |
| | THAN TWO WINDOWS.THE DESCRIPTION STATES THAT THE |
| | DESCRIPTION IS "CLEMATIS GARAGE - ELECTRIC" BUT THE |
| | ENERGY CALC NEEDS TO SHOW ALL BUILDING COMPONENTS AS |
| | REQUIRED. |
| | |
| | 3.OWNER/AGENT IS TO SIGN THE ENERGY CALCS PRIOR TO |
| | SUBMITTAL, FBC13-103.1. |
| | |
| | 4.SEE ENERGY CALC PAGE WITH "OTHER REQUIRED |
| | COMPLIANCE" TITLE, SHEET 7.PLEASE COMPLETE. |
| | |
| | 5.NOTHING IS SHOWN IN THE COMPONENT "FLOORS", PAGE 5 |
| | OF THE ENERGY CALC, BUT CONFERENCE ROOM AND OFFICES |
| | HAVE A FLOOR OVER UNCONDITIONED SPACE. |
| | |
| | 6.THIS IS NOT AN EXHAUSTIVE LIST AS ENERGY CALCS ARE |
| | SPOT CHECKED FOR COMPLIANCE.PLEASE CHECK ALL |
| | COMPONENTS AND CONFIRM THAT INSULATION ON THE ENERGY |
| | CALC MATCHES INSULATION ON THE PLAN. |
| | |
| | PURSUANT TO CONTRACTOR'S REQUEST, THE PERMIT WILL BE |
| | ISSUED WITH THE FOLLOWING PROVISOS: |
| | |
| | 1.PROVIDE PRECAST FASTENING (ITEM 23B) |
| | |
| | 2.PROVIDE METHOD OF ATTACHMENT PRECAST PILASTER (ITEM |
| | 26) |
| | |
| | 3.APPLY FOR LOCAL PRODUCT APPROVAL, INGERSOLL RAND |
| | REPORT S07-001 (29A) |
| | |
| | 4.REVISE FIRE RESISTIVE DESIGN SHEETS (LS1-D1 THROUGH |
| | 3) TO INCLUDE UL U905 AND UL U926. |
| | |
| | 5.REVISE DETAIL C4 A5-D.1 TO INCLUDE UL ASSEMBLY OR |
| | CALCULATED FIRE RESISTANCE. |
| | |
| | 6.SUBMIT PRODUCT APPROVAL FOR DOORS IN ZONE 5. |
| | |