| Date |
Text |
| 2007-12-27 10:42:05 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. SHT IR.1 SHOW THE LOCATION OF THE WATER SOURCE. IF |
| | IT IS POTABLE WATER FROM THE CITY, SHOW THE WATER METER |
| | LOCATION AND THE RPZV BACKFLOW LOCATION.THE NOTE |
| | "CONNECT TO EXISTING SYSTEM". WHAT EXISTING SYSTEM? |
| | PLEASE SHOW ALL PIPING FOR THE COMPLETE SYSTEM.(METER |
| | 2 LOCATION IS INDICATED. IS THERE ANOTHER METER?). |
| | PLEASE CLARIFY. SECTIONS 106.1.1 & 106.1.2. |
| | |
| | 2. SHT IR.1 SOME INFORMATION ON THE SHEET IS NOT |
| | LEGIBLE. PLEASE MAKE ALL INFORMATION LEGIBLE. SECTION |
| | 106.1.1. |
| | |
| | 3. SHT IR.1 SHOWS CONTROLLER B,AND THE LEGEND |
| | INDICATES A RAIN SENSOR ONE PER EACH CONTROLLER. PLEASE |
| | CLARIFY. IS THERE MORE THAN ONE CONTROLLER. IF SO |
| | PLEASE INDICATE THE LOCATION OF EACH CONTROLLER. |
| | SECTION 106.1.1. |
| | |
| | 4. SHTS IR.1 & IR.2 ARE REQUIRED TO SEALED WITH AN |
| | EMBOSSED TYPE SEAL THAT WILL IMPRESS ALL REQUIRED |
| | INFORMATION ON EACH SHEET. A STAMP SEAL IS NOT |
| | APPROVED. SECTION 106.1. FAC 61G1-16.001 & 61G1-16.002 |
| | INDICATE THE REQUIREMENTS OF THE SEAL. PLEASE COMPLY. |
| | FS 481.306. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING |
| | THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE |
| | ALL VOID SHEETS FROM ALL PLANS AND PLACE |
| | ONE SET OF THEM LOOSELY ON TOP OF THE |
| | COLLATED PLANS TO BE REVIEWED. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |