| 2008-04-10 15:41:27 | BUILDING PLAN REVIEW |
| | PERMIT: 07090747 |
| | ADD: 307 EVERNIA STREET #100 |
| | CONT: G3 CONST. |
| | TEL: (561)393-3939 |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 4-10-08 |
| | REVIEW: REVISION |
| | ACTION: DENIED |
| | |
| | NOTE: THESE NOTES ARRE IN REFERENCE TO THE EXHAUST WALL |
| | CAP WITH WMS ON SHEET M1.1 |
| | |
| | 1)FBC 1403.2 THE EXTERIOR WALL ENVELOPE SHALL BE |
| | DESIGNED AND CONSTRUCTED IN SUCH A MANNER AS TO PREVENT |
| | THE ACCUMULATION OF WATER WITHIN THE WALL ASSEMBLY BY |
| | PROVIDING A WATER-RESISTIVE BARRIER BEHIND THE EXTERIOR |
| | VENEER, AS DESCRIBED IN SECTION 1404.2 AND A MEANS FOR |
| | DRAINING WATER THAT ENTERS THE ASSEMBLY TO THE EXTERIOR |
| | OF THE VENEER, UNLESS IT IS DETERMINED THAT PENETRATION |
| | OF WATER BEHIND THE VENEER SHALL NOT BE DETRIMENTAL TO |
| | THE BUILDING PERFORMANCE. |
| | |
| | 2)FBC 1203. NATURAL VENTILATION OF AN OCCUPIED SPACE |
| | SHALL BE THROUGH WINDOWS, DOORS, LOUVERS OR OTHER |
| | OPENINGS TO THE OUTDOORS. THE OPERATING MECHANISM FOR |
| | SUCH OPENINGS SHALL BE PROVIDED WITH READY ACCESS SO |
| | THAT THE OPENINGS ARE READILY CONTROLLABLE BY THE |
| | BUILDING OCCUPANTS. |
| | |
| | 3)1609.1.4 (5.) LOUVERS PROTECTING INTAKE AND EXHAUST |
| | VENTILATION DUCTS NOT ASSUMED TO BE OPEN THAT ARE |
| | LOCATED WITHIN 30 FEET OF GRADE SHALL MEET REQUIREMENTS |
| | OF THE LARGE MISSILE TEST. |
| | IMPACT-RESISTANT COVERINGS SHALL BE TESTED AT 1.5 TIMES |
| | THE DESIGN PRESSURE (POSITIVE OR NEGATIVE) EXPRESSED IN |
| | POUNDS PER SQUARE FEET AS DETERMINED BY THE FLORIDA |
| | BUILDING CODE, BUILDING SECTION 1609 FOR WHICH THE |
| | SPECIMEN IS TO BE TESTED. |
| | |
| | 4)PROVIDE PRODUCT APPROVAL FOR THE LOUVER PER DCA |
| | RULE 9B-72, WHICH STATES ?THOSE PRODUCTS WHICH ARE |
| | REGULATED BY DCA SHALL BE REVIEWED AND APPROVED IN |
| | WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| | SUBMIT TWO COPIES OF PRODUCT APPROVAL FOR THE LOUVER |
| | AND SHOW HOW IT WILL PREVENT WATER INTRUSION. |
| | |
| | MYRON JACOBS |
| | BUILDING PLAN REVIEWER |