2008-02-14 08:50:03PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 ** MECHANICAL REVISION PAGE M1.1 **
  
 *** DENIED ***
 1) THE A/C CONDENSATE LINE MAY NOT CONNECT INTO THE
 STORM RISER AT THAT POINT, IT MUST GO TEN FEET FROM THE
 BUILDING THEN TIE-IN TO THE STORM RISER WITH A RELIEF
 VENT. ALSO A CHECK VALVE WOULD STOP THE CONDENSATE
 WATER FROM GETTING PAST AS IT IS NOT UNDER PRESSURE.
 THERE ARE ALSO OTHER OPTIONS TO DISPOSE OF THE
 CONDENSATE WATER. PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;