2007-12-19 12:21:39** DENIED 3RD REVIEW **
  
  
 1) NOTE: PLEASE SEE BOTH SETS OF PLANS SUBMITTED
 CONTAIN REVISED ARCHITECTURAL AND ELECTRICAL SHEETS
 WHICH ARE NOT SIGNED, DATED OR SEALED BY THE
 RESPONSIBLE DESIGNERS OF RECORD.
 PLEASE SEE FAC 61G1-16, 61G15-23.002, FS 471.025 AND
 481.221.
  
 2) NOTE: PLEASE SEE PLANS ARE NOW INDICATING ON SOME OF
 THE ARCHITECTURAL SHEETS THAT NO FIRE RATE WALLS WILL
 BE PROVIDED AND WIRING METHODS SHALL MEET CHAPTERS 1-4
 OF THE ELECTRICAL CODE.
 PLEASE SEE THAT PLANS SPECIFICALLY STILL STATE DESIGN
 IS TO MEET NFPA-75 2003 WHEN THIS IS APPARENTLY NOT THE
 DESIGN SHOWN ON PLANS.
 PLEASE BE SURE THE ELECTRICAL PLANS STATE THE WIRING
 METHODS AND REMOVE ANY ?IT? ROOM OR EQUIPMENT
 DESIGNATIONS. AS THIS IS NOT AN IT ROOM, ALL WIRING
 METHODS SHALL MEET THE MORE RESTRICTIVE CODES AS NOTED
 ABOVE.
 BELOW IS THE COMMENTARY TO 645.4
 **USE OF THE REQUIREMENTS IN ARTICLE 645 IS BASED ON
 THE ASSUMPTION THAT CONSTRUCTION OF THE INFORMATION
 TECHNOLOGY EQUIPMENT (ITE) ROOM COMPLIES WITH NFPA 75,
 STANDARD FOR THE PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT. FOR THOSE ITE ROOMS CONSTRUCTED IN
 ACCORDANCE WITH NFPA 75, ARTICLE 645 CONTAINS
 ELECTRICAL INSTALLATION REQUIREMENTS THAT ARE LESS
 STRINGENT THAN THE REQUIREMENTS IN THE FIRST FOUR
 CHAPTERS OF THE CODE. APPLICATION OF THESE PROVISIONS
 IS CONTINGENT ON THE ITE ROOM CONSTRUCTION AND
 EQUIPMENT MEETING ALL FIVE PROVISIONS SPECIFIED IN
 645.4. FOR EXAMPLE, THE PROVISIONS FOR WIRING
 INSTALLATIONS IN THE SPACE BENEATH THE RAISED FLOOR OF
 AN ITE ROOM WHERE THAT SPACE IS ALSO USED FOR
 ENVIRONMENTAL AIR ARE LESS STRINGENT THAN THOSE IN
 CHAPTERS 1 THROUGH 4 FOR THAT SAME TYPE OF SPACE. THE
 LESS RESTRICTIVE PROVISIONS IN ARTICLE 645 CANNOT BE
 TAKEN ADVANTAGE OF IF ANY ONE OF THE CONDITIONS
 SPECIFIED IN 645.4 IS ABSENT.**
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.