2007-11-27 16:06:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 10-18-07.THE JOB ADDRESS
 NEED TO BE IN THE TITLE BLOCK OF EACH PAGE OF THE
 PLANS, SEE W.P.B. 106.1.3. SEE MECHANICAL PLAN PAGE
 M1.1 MISSING ADDRESS.
  
 2) PLAN A1-3STATES,NEW CONDENSING UNIT FOR NEW
 LIEBERT A/C SYSTEM, ETC. ETC. AND ENDS WITH "VERIFY
 WITH ENGINEER". NO ENGINEERING WITH WIND LOAD
 CALCULATIONS SHOWING THAT THE TRELLIS WITH THE
 CONDENSER UNIT ON TOP WILL WITHSTAND 140 MPH WINDS WAS
 SUBMITTED. PLEASE COMPLY WITH 2004 FBC 1609 AS
 REQUESTED IN LAST REVIEW 10-18-07.
  
 3)SEE ATTACHED NOTICE FS 553.80 (2) (B) REGARDING
 FOUR TIMES THE FEE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]