Plan Review Notes
Plan Review Notes For Permit 07090747
Permit Number 07090747
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2007-11-29 12:52:43*****DENIED*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADRESSED:
  
 1.THE COMPLETE ADDRESS OF THE PROJECT SITE, INCLUDING
 SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.ADDRESS MISSING ON SHEETS
 FP1.1, M1.1
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. ADD
 COMMENT TO SHEET D1-1
  
 3.THE BUILDING AND/OR TENANT SPACE SHALL BE PERMITTED
 TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED. ADD
 COMMENT TO SHEET D1-1
  
 4.WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION
 OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE
 SYSTEM SHALL BE KEPT IN SERVICE AND THE FIRE DEPARTMENT
 SHALL BE NOTIFIED.ADD COMMENT TO SHEET FP1-1
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 NEW FM-200 FIRE SUPPRESSION SYSTEM.ADD COMMENT TO
 SHEET A1-3
  
 8.THE NEW FIRE DOOR AND WINDOW SHALL BE IN ACCORDANCE
 WITH NFPA 80.ADD COMMENT TO SHEET A1-3
  
  
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW