| Plan Review Notes For Permit 07090747 |
| Permit Number |
07090747 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-29 12:52:43 | *****DENIED***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADRESSED: | | | | | | 1.THE COMPLETE ADDRESS OF THE PROJECT SITE, INCLUDING | | | SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH | | | SUBMITTED PLAN SHEET.ADDRESS MISSING ON SHEETS | | | FP1.1, M1.1 | | | | | | 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. ADD | | | COMMENT TO SHEET D1-1 | | | | | | 3.THE BUILDING AND/OR TENANT SPACE SHALL BE PERMITTED | | | TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY WHERE | | | REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION | | | FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED. ADD | | | COMMENT TO SHEET D1-1 | | | | | | 4.WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION | | | OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE | | | SYSTEM SHALL BE KEPT IN SERVICE AND THE FIRE DEPARTMENT | | | SHALL BE NOTIFIED.ADD COMMENT TO SHEET FP1-1 | | | | | | 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE | | | NEW FM-200 FIRE SUPPRESSION SYSTEM.ADD COMMENT TO | | | SHEET A1-3 | | | | | | 8.THE NEW FIRE DOOR AND WINDOW SHALL BE IN ACCORDANCE | | | WITH NFPA 80.ADD COMMENT TO SHEET A1-3 | | | | | | | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS | | | ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|