Plan Review Notes
Plan Review Notes For Permit 07090747
Permit Number 07090747
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-18 23:43:00*****DENIED*****
  
  
 1.THE COMPLETE ADDRESS OF THE PROJECT SITE, INCLUDING
 SUITE NUMBER, SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.THE BUILDING AND/OR TENANT SPACE SHALL BE PERMITTED
 TO BE OCCUPIED DURING THE SCOPE OF WORK ONLY WHERE
 REQUIRED MEANS OF EGRESS AND REQUIRED FIRE PROTECTION
 FEATURES ARE IN PLACE AND CONTINUOUSLY MAINTAINED.
  
 4.WHERE ALTERATION REQUIRES MODIFICATION OF A PORTION
 OF THE FIRE PROTECTION SYSTEM, THE REMAINDER OF THE
 SYSTEM SHALL BE KEPT IN SERVICE AND THE FIRE DEPARTMENT
 SHALL BE NOTIFIED.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION AND THE
 FLORIDA FIRE PREVENTION CODE 2004 SHALL BE REFERENCED.
  
 6.NFPA 75,PROTECTION OF INFORMATION TECHNOLOGY
 EQUIPMENT, 2003 EDITION SHALL BE REFERENCED.
  
 7.SEPARATE PLANS AND PERMIT WILL BE REQUIRED FOR THE
 NEW FM-200 FIRE SUPPRESSION SYSTEM.
  
 8.THE NEW FIRE DOOR AND WINDOW SHALL BE IN ACCORDANCE
 WITH NFPA 80.
  
 9.SPECIFY THE NEW WALL AND CEILING FINISH MATERIALS
 IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  