Plan Review Notes
Plan Review Notes For Permit 07090747
Permit Number 07090747
Review Stop E
Sequence Number 1
Notes
Date Text
2007-10-16 10:37:56**** DENIED ****
  
  
 1) NOTE: ** PERMIT APPLICATION NEEDS TO INDICATE THE
 FLOOR/SUITE/UNIT # IN WHICH THE WORK IS BEING DONE.
 THIS WILL NEED TO BE CORRECTED IN OUR SYSTEM AS WELL
 AND APPLICATION.
 FBC 110.1.2, FAC 61G1-16.004, 61G15-23.002
  
 2) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS.
 2003 NFPA-75
  
 ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR
 CODES.
  
 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK IS TO INCLUDE ALL LABOR, ALL MATERIALS, AND ALL
 EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ARE
 OWNER SUPPLIED.
 THIS INCLUDES IT EQUIPMENT.
 FBC 108.3
 ** PLEASE KNOW AS THE CERTAIN SUB PERMITS (ELECTRICAL)
 DO NOT PAY FEES BASED ON VALUE, THE COMPLETE SCOPE OF
 WORK VALUE SHALL BE ON BASE PERMIT.
 PLEASE SEE COMMENTS FROM OTHER TRADES WHICH ALSO MAY BE
 NOTED.
  
 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE MTS.
 90.7, 110.3
 FBC 106.1.2
  
 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT
 SHEETS FOR THE PROPOSED IT EQUIPMENT. 90.7, 110.3
 PLEASE BE SURE ALL SPECS/CUT SHEETS CONTAIN LISTINGS
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY.
 (NRTL).
 PLEASE CLARIFY IF THERE WILL BE ANY UPS EQUIPMENT?
 645.11
 PLEASE CLARIFY THE PLANS WHICH INDICATE A CONTROL PANEL
 HOWEVER IT IS NOT CLEAR WHAT THIS CONTROL PANEL DOES.
 PLEASE SEE 645.10 FOR POSSIBLE DISCONNECTING MEANS OF
 ELECTRICAL EQUIPMENT IN ROOM WHICH.
 PLEASE KNOW AT THIS TIME SOME ITEMS CAN NOT BE REVIEWED
 FOR CODE COMPLIANCE.
  
 6) NOTE: PLEASE COMPLETE LIGHTING POWER DENSITIES FOR
 NEW LIGHTING IN ROOM.
 13-415.2
  
 7) NOTE: PLEASE SEE THAT ANY NEW LIGHTING CONTROL
 DEVICES WILL BE REQUIRED TO MEET 13-415.1.ABC.1.1/.1.2.
 THIS IS ONLY FOR THE NEW ROOM AND LIGHTING CONTROL FOR
 THAT ROOM.
  
 8) NOTE: PLEASE SEE RISER WHICH SHOWS AN OCTAGONAL NOTE
 #7 WHICH ON FEEDER SCHEDULE MENTIONS #4 FOR EQUIPMENT
 GROUND. THE RISER SHOWS #3 WITH THE 500MCM WHICH IS
 CORRECT PER 250.122 HOWEVER THE #4 AS ON KEY NOTES IS
 TOO SMALL.
 PLEASE ADJUST.
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE
 PRESENT AT THIS TIME.
  
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL
 PLANS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved