| Date |
Text |
| 2007-10-16 10:37:56 | **** DENIED **** |
| | |
| | |
| | 1) NOTE: ** PERMIT APPLICATION NEEDS TO INDICATE THE |
| | FLOOR/SUITE/UNIT # IN WHICH THE WORK IS BEING DONE. |
| | THIS WILL NEED TO BE CORRECTED IN OUR SYSTEM AS WELL |
| | AND APPLICATION. |
| | FBC 110.1.2, FAC 61G1-16.004, 61G15-23.002 |
| | |
| | 2) NOTE:PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| | CODES ARE STATED ON PLANS. |
| | 2003 NFPA-75 |
| | |
| | ** PLEASE BE SURE TO SEE COMMENTS FROM OTHER TRADES FOR |
| | CODES. |
| | |
| | 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF |
| | WORK IS TO INCLUDE ALL LABOR, ALL MATERIALS, AND ALL |
| | EQUIPMENT, DESIGN COST ETC EVEN IF ANY OF THESE ARE |
| | OWNER SUPPLIED. |
| | THIS INCLUDES IT EQUIPMENT. |
| | FBC 108.3 |
| | ** PLEASE KNOW AS THE CERTAIN SUB PERMITS (ELECTRICAL) |
| | DO NOT PAY FEES BASED ON VALUE, THE COMPLETE SCOPE OF |
| | WORK VALUE SHALL BE ON BASE PERMIT. |
| | PLEASE SEE COMMENTS FROM OTHER TRADES WHICH ALSO MAY BE |
| | NOTED. |
| | |
| | 4) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE MTS. |
| | 90.7, 110.3 |
| | FBC 106.1.2 |
| | |
| | 5) NOTE: PLEASE SUBMIT THE MANUFACTURES SPECS/CUT |
| | SHEETS FOR THE PROPOSED IT EQUIPMENT. 90.7, 110.3 |
| | PLEASE BE SURE ALL SPECS/CUT SHEETS CONTAIN LISTINGS |
| | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY. |
| | (NRTL). |
| | PLEASE CLARIFY IF THERE WILL BE ANY UPS EQUIPMENT? |
| | 645.11 |
| | PLEASE CLARIFY THE PLANS WHICH INDICATE A CONTROL PANEL |
| | HOWEVER IT IS NOT CLEAR WHAT THIS CONTROL PANEL DOES. |
| | PLEASE SEE 645.10 FOR POSSIBLE DISCONNECTING MEANS OF |
| | ELECTRICAL EQUIPMENT IN ROOM WHICH. |
| | PLEASE KNOW AT THIS TIME SOME ITEMS CAN NOT BE REVIEWED |
| | FOR CODE COMPLIANCE. |
| | |
| | 6) NOTE: PLEASE COMPLETE LIGHTING POWER DENSITIES FOR |
| | NEW LIGHTING IN ROOM. |
| | 13-415.2 |
| | |
| | 7) NOTE: PLEASE SEE THAT ANY NEW LIGHTING CONTROL |
| | DEVICES WILL BE REQUIRED TO MEET 13-415.1.ABC.1.1/.1.2. |
| | THIS IS ONLY FOR THE NEW ROOM AND LIGHTING CONTROL FOR |
| | THAT ROOM. |
| | |
| | 8) NOTE: PLEASE SEE RISER WHICH SHOWS AN OCTAGONAL NOTE |
| | #7 WHICH ON FEEDER SCHEDULE MENTIONS #4 FOR EQUIPMENT |
| | GROUND. THE RISER SHOWS #3 WITH THE 500MCM WHICH IS |
| | CORRECT PER 250.122 HOWEVER THE #4 AS ON KEY NOTES IS |
| | TOO SMALL. |
| | PLEASE ADJUST. |
| | |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET |
| | COMPLETED ON PLANS FOR REVIEW, NOT ALL COMMENTS MAY BE |
| | PRESENT AT THIS TIME. |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |