Text |
| 2007-11-19 07:47:51 | |
| | |
| | APPLICATION #07090742 |
| | ELECTRICAL PLAN REVIEW |
| | 6793 SPARROW HAWK DRIVE |
| | 11/19/07 |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | ARTICLES REFERENCED ARE 2005 NEC UNLESS OTHERWISE |
| | NOTED. |
| | |
| | ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE |
| | NOTED. |
| | |
| | THESE COMMENTS ARE FROM THE PREVIOUS REVIEW. |
| | |
| | 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE |
| | 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE |
| | CURRENT EDITION ADOPTED BY THE STATE. *HAND DRAWN |
| | CHANGES TO THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE |
| | DETERMINED THAT THE CHANGES WERE MADE WITH THE |
| | KNOWLEDGE OR CONSENT OF THE DESIGNER OF RECORD. 106.1.3 |
| | FBC AS AMENDED. |
| | |
| | 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B" |
| | IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80 |
| | WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE |
| | INCREASED TO 1 1/4" TO MEET MINIMUM SIZE FOR FILL |
| | REQUIREMENTS OF ARTICLE 352.22. *HAND DRAWN CHANGES TO |
| | THE PLAN ARE UNACCEPTABLE AS IT CANNOT BE DETERMINED |
| | THAT THE CHANGES WERE MADE WITH THE KNOWLEDGE OR |
| | CONSENT OF THE DESIGNER OF RECORD. 106.1.3 FBC AS |
| | AMENDED. |
| | |
| | 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS. |
| | SEE 61G1-16.001 FAC. *THE INFORMATION ON THE SEAL STILL |
| | CANNOT BE READ. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |