| 2007-09-28 10:24:04 | DENIED; | | | RISER DIAGRAM DOES NOT MATCH FLAT DRAWING. | | | A) BATH #2 SHOWER IS PART OF THE BATHROOM GROUP | | | ON RISER DIAGRAM PART OF THE 1/2 BATH ON FLOOR PLAN | | | WITH OWN VENT. | | | B) KITCHEN, RISER DIAGRAM SHOWS A LOOP VENT, | | | FLAT DRAWING DOES NOT. | | | C) MASTER BATH RISER DIAGRAM DOES NOT MATCH FLAT | | | DRAWING | | | RISER DIAGRAM SHOWS 2" AT BASE OF WAHER STACK WITH A 3" | | | VENT THOUGH ROOF. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|