| 2007-09-28 09:49:02 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) ENERGY CALCULATIONS LINE 11B STATES THE AIR HANDLER |
| | IS INSTALLED IN THE INTERIOR, BUT THE PLANS SHOW THE |
| | AIR HANDLER TO BE INSTALLED IN THE ATTIC, THE TWO MUST |
| | COINCIDE. SEE F.B.C. 106.1.1CONSTRUCTION DOCUMENTS |
| | SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE AND RELEVANT LAWS. PLEASE CORRECT. |
| | |
| | 2) COOLING LOAD CALCULATIONS SHOW SYSTEM ONE TOTAL |
| | COOLING BTU'S TO BE 34,112, MECHANICAL PLANS SHOW |
| | SYSTEM ONE TO BE 46,500 TOTAL BTU'S. PER F.B.C. |
| | 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE |
| | TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS, |
| | PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 3 |
| | TON SYSTEM MAYMEET THIS REQUIREMENT). |
| | |
| | 3) COOLING LOAD CALCULATIONS SHOW SYSTEM TWO TOTAL |
| | COOLING BTU'S TO BE 20,318, MECHANICAL PLANS SHOW |
| | SYSTEM TWO TO BE 29,200 TOTAL BTU'S. PER F.B.C. |
| | 13-607.1.ABC.1.1 THE PLANS MAY ONLY CALL FOR 15% MORE |
| | TOTAL COOLING BTU'S THEN THE COOLING LOAD CALCULATIONS, |
| | PLEASE CORRECT. (SEE ATTACHED ARI SHEET THAT SHOWS A 2 |
| | TON SYSTEM MAYMEET THIS REQUIREMENT). |
| | |
| | 4) SEE MECHANICAL PLAN EQUIPMENT SCHEDULE, MODEL |
| | NUMBERS FOR THE CONDENSER UNITS COULD NOT BE FOUND IN |
| | THE ARI DIRECTORY, PLEASE CORRECT AND PROVIDE A ARI |
| | REFERENCE SHEET, SEE W.P.B AMEND. 106.2. |
| | |
| | MECHANICAL PLAN REVIEW BY; |
| | TOM GORDON (561) 805-6729 |
| | E-MAIL; [email protected] |