| | APPLICATION #07090742 |
| | ELECTRICAL PLAN REVIEW |
| | 6793 SPARROW HAWK DRIVE |
| | |
| | WEST PALM BEACH, FL. |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1, AND |
| | FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | ALL COMMENTS RELATE TO SHEET A-3.0, UNLESS OTHERWISE |
| | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS |
| | OTHERWISE NOTED. |
| | |
| | 1} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT |
| | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE |
| | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS |
| | EQUAL TO OR GREATER |
| | THAN THE AVAILABLE FAULT. |
| | |
| | 2} THE 13000VA HEAT CALCULATION GIVEN IN PANEL "A" DOES |
| | NOT CORRELATE TO THE 10000 VA LOADS SHOWN IN THE PANEL |
| | SCHEDULE OR IN THE MECHANICAL SPECIFICATIONS. |
| | |
| | 3} THE 6' GROUND ROD INDICATED ON THE RISER DIAGRAM IS |
| | NOT IN COMPLIANCE WITH 250.53(G) "THE ELECTRODE SHALL |
| | BE INSTALLED SUCH THAT AT LEAST 2.44 M (8 FT) OF LENGTH |
| | IS IN CONTACT WITH THE SOIL". |
| | |
| | 4} IN THE "ELECTRICAL LEGEND" FOR AFI RECEPTACLES THE |
| | 2002 NEC IS INCORRECTLY REFERENCED. THE 2005 NEC IS THE |
| | CURRENT EDITION ADOPTED BY THE STATE. |
| | |
| | 5} IF THE PVC CONDUIT FEED FROM PANEL "A" TO PANEL "B" |
| | IS EXPOSED TO PHYSICAL DAMAGE PER 352.10(F) SCHEDULE 80 |
| | WOULD BE REQUIRED. THE SCHEDULE 80 WOULD NEED TO BE |
| | INCREASED TO 1 1/4"TO MEET MINIMUM SIZE FOR FILL |
| | REQUIREMENTS OF ARTICLE 352.22. |
| | |
| | 6} THE ELECTRICAL NOTES ON SHEET D-1 INDICATE #12 |
| | CONDUCTORS WILL BE THE MINIMUM SIZE FOR THIS PROJECT, |
| | THE PANEL SCHEDULE FOR PANEL "A" LISTS SEVERAL #14 |
| | CONDUCTORS FOR BRANCH CIRCUITS. PLEASE CORRELATE SAME. |
| | |
| | 7} THE ARCHITECTS SEAL IS INDISCERNIBLE, ALL SHEETS. |
| | SEE 61G1-16.001 FAC. |
| | |
| | 8} THE SIGNATURE OF THE REVIEWER FOR GFA CANNOT BE READ |
| | DUE TO THE LOCATION IN THE COMPLIANCE BLOCK. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |