| Plan Review Notes For Permit 07090740 |
| Permit Number |
07090740 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-04 17:31:09 | DENIED BY BUILDING | | | | | | 1) THE ROOF WIND PRESSURE AND ATTACHMENT DESIGN | | | ENGINEERING THAT WAS SUBMITTED IS BASED ON EXPOSURE B, | | | HOWEVER, THE STRUCTURAL PLANS SPECIFY EXPOSURE C. SEE | | | SHEET S-12 OF PERMITTED PLANS. PLEASE SUBMIT | | | CALCULATIONS FOR EXPOSURE C OR REVISE THE STRUCTURAL | | | PLANS TO EXPOSURE B. FBC 1609.4. | | | | | | 2) SUBMIT 3 COPIES OF SUBMITTALS. CITY AMENDMENTS FBC | | | 109.3.6 THRESHOLD BUILDING. | | | | | | 3) THE ROOFING PRODUCT APPROVAL SUBMITTED SPECIFIES A | | | DIFFERENT ASSEMBLY THAN THE ONE THAT WAS SPECIFIED FOR | | | THE MASTER PERMIT. THEREFORE, A REVISION FEE OF $60.00 | | | IS REQUIRED. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|