Plan Review Notes
Plan Review Notes For Permit 07090731
Permit Number 07090731
Review Stop M
Sequence Number 1
Notes
Date Text
2007-10-15 09:13:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R,
 PER 2004 FBC 13-600.3.A, (12-8-06 REVISION).
  
 2) MECHANICAL PERMIT #07090733 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE ADJUST VALUE OF WORK TO BE DONE TO SHOW THE
 FAIR MARKET VALUE OR THE CITY WILL NEED TO ADJUST THE
 VALUE USING MARSHALL AND SWIFT SEGREGATED COST METHOD,
 PER CITY W.P.B. AMEND. 108.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]