| 2007-10-02 09:41:34 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} THE VALUE ON THE APPLICATION MUST INCLUDE THE TOTAL |
| | COST OF LABOR AND MATERIAL. VALUATION REFERENCES MAY |
| | INCLUDE THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES PER 108.3 FBC AS |
| | AMENDED. |
| | |
| | A PERMIT SHALL NOT BE ISSUED UNTIL FEES AUTHORIZED |
| | UNDER SECTION 553.80, FLORIDA STATUTES, HAVE BEEN PAID. |
| | 108.1 FBC. |
| | |
| | ADJUST THE VALUE AT THE PERMIT CLERK?S DESK, AND PAY |
| | THE DIFFERENCE IN FEES PRIOR TO RESUBMITTING. |
| | |
| | 2} SHEET #2 INDICATES " ELECTRIC METER AND DISCONNECT" |
| | THE RISER DIAGRAM ON SHEET #5SHOWS A METER AND A PANEL. |
| | CORRELATE SAME. |
| | |
| | 3} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION |
| | ON THE APPLICATION, PROVIDE AN AIC RATING, AND LOCATE |
| | ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, |
| | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER |
| | DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE. |
| | |
| | 4} SHOW THE LOCATION OF THE A/C CONDENSER ON THE PLAN. |
| | ALSO SHOW COMPLIANCE WITH THE REQUIRED DISCONNECT PER |
| | 440.14,RECEPTACLE PER 210.63. |
| | |
| | 5} KITCHEN RECEPTACLE SPACING MUST COMPLY WITH |
| | 210.52(A), 210.52(C), AND 210.8(A)(6) GFI. ADD NEXT TO |
| | THE RANGE. |
| | |
| | 6} IN DWELLING UNITS, HALLWAYS OF 3.0 M (10 FT) OR MORE |
| | IN LENGTH SHALL HAVE AT LEAST ONE RECEPTACLE OUTLET. |
| | 210.52(H) |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | [email protected] |
| | |
| | |