Plan Review Notes
Plan Review Notes For Permit 07090711
Permit Number 07090711
Review Stop E
Sequence Number 4
Notes
Date Text
2008-02-26 11:53:15 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} 230.70(A) (1)READILY ACCESSIBLE LOCATION THE
 SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A
 READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A
 BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF
 ENTRANCE OF THE SERVICE CONDUCTORS.DO TO CONDITIONS NOW
 REQUIREING CONDUITS BE RAN THROUGH THE BUILDING
 UNPROTECTED, AND GIVEN THE FACT OF DIFFERING VOLTAGES
 ALLOWED PER 230.2(D) THE METER AND DISCONNECT WILL BE
 ALLOWED OUTSIDE THE BUILDING GROUPED WITH THE MANUAL
 TRANSFER SWITH SHOWN ON SHEET E2. ALSO NOTE THAT
 IDENTIFICATION PER 230.2(E) IS REQUIRED. INDICATE THESE
 CHANGES ON RESUBMITTED PLANS.
  
 2} SEE BUILDING COMMENTS REGARDING CONDUITS IN THE
 STAIRWELL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718