| Plan Review Notes For Permit 07090711 |
| Permit Number |
07090711 |
|
| Review Stop |
E |
| Sequence Number |
4 |
|
| Notes |
| Date |
Text |
| 2008-02-26 11:53:15 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} 230.70(A) (1)READILY ACCESSIBLE LOCATION THE | | | SERVICE DISCONNECTING MEANS SHALL BE INSTALLED AT A | | | READILY ACCESSIBLE LOCATION EITHER OUTSIDE OF A | | | BUILDING OR STRUCTURE OR INSIDE NEAREST THE POINT OF | | | ENTRANCE OF THE SERVICE CONDUCTORS.DO TO CONDITIONS NOW | | | REQUIREING CONDUITS BE RAN THROUGH THE BUILDING | | | UNPROTECTED, AND GIVEN THE FACT OF DIFFERING VOLTAGES | | | ALLOWED PER 230.2(D) THE METER AND DISCONNECT WILL BE | | | ALLOWED OUTSIDE THE BUILDING GROUPED WITH THE MANUAL | | | TRANSFER SWITH SHOWN ON SHEET E2. ALSO NOTE THAT | | | IDENTIFICATION PER 230.2(E) IS REQUIRED. INDICATE THESE | | | CHANGES ON RESUBMITTED PLANS. | | | | | | 2} SEE BUILDING COMMENTS REGARDING CONDUITS IN THE | | | STAIRWELL. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|