2008-03-07 09:06:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.PLEASE HAVE THE ENGINEER ALBERT RHUI-HONG TENG
 CONTACT ME.I HAVE HAD CONVERSATIONS WITH HIS OFFICE
 REGARDING THE LIFE SAFETY ISSUE OF NON REQUIRED ITEMS
 IN A PROTECTED STAIR, FBC1019.1.THE ELECTRIC RUNNING
 THROUGH THE STAIRWELL WAS REMOVED, BUT NOW IT IS SHOWN
 AGAIN AS PENETRATING THE PROTECTED STAIR.IT IS NOT
 CLEAR WHY THE ENGINEER IS SEALING A PLAN WITH A LIFE
 SAFETY ISSUE WHICH HAS ALREADY BEEN BROUGHT TO HIS
 ATTENTION.IS THIS NOT A PROTECTED EXIT STAIR?
  
 A SET HAS BEEN RETAINED.
  