Plan Review Notes
Plan Review Notes For Permit 07090711
Permit Number 07090711
Review Stop E
Sequence Number 3
Notes
Date Text
2008-01-28 09:29:52 
  
  
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE REGARDING NOTES AND DRAWING
 ON SHEET E2: AND WERE NOT CORRECTLY RESPONDED TO FROM
 THE LAST REVIEW. NOTE: FURTHER EXPLANATION OF THE
 COMMENTS IS MARKED BY AN ASTERISK.
  
 1} 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. INDICATE UNDER WHICH EXCEPTION YOU ARE
 ASKING THE AHJ FOR PERMISSION FOR THIS SERVICE.* THIS
 COMMENT WAS NOT ADDRESSED, ONLY THE PROPOSED SERVICE IS
 SHOWN, NOT THE OTHER SERVICE(S) FOR THE BUILDING.
  
 2} INDICATE COMPLIANCE WITH 230.71 MAXIMUM NUMBER OF
 DISCONNECTS, AND 230.72 GROUPING OF DISCONNECTS.* SAME
 COMMENT AS ABOVE, THE OTHER SERVICE(S) ARE NOT SHOWN
 THERREFORE COMPLIANCE WITH THIS ARTICLE CANNOT BE
 REVIEWED.
  
 4} 250.24(D) GROUNDING ELECTRODE CONDUCTOR- A GROUNDING
 ELECTRODE CONDUCTOR SHALL BE USED TO CONNECT THE
 EQUIPMENT GROUNDING CONDUCTORS, THE SERVICE-EQUIPMENT
 ENCLOSURES, AND, WHERE THE SYSTEM IS GROUNDED, THE
 GROUNDED SERVICE CONDUCTOR TO THE GROUNDING
 ELECTRODE(S) REQUIRED BY PART III OF THIS ARTICLE.
 THERE IS NONE INDICATED ON THE PROPOSED SERVICE. SEE
 250.24(C) FOR POINT OF ATTACHMENT, SEE 250.66 FOR
 SIZING REQUIREMENTS.* INDICATING A GROUND ROD ON THE
 RISER DIAGRAM DOES NOT MEET THE REQUIREMENT OF THIS
 ARTICLE.IF THIS SERVICE IS GROUPED PER 230.72, AND
 ALLOWED BY EXCEPTION THEN THE GEC SHALL BE CONNECTED TO
 THE EXISTING GEC.PER THIS ARTICLE.
  
 NEW COMMENT:
  
 5} THE ENGINEERS SEAL IS NOT CORRECTLY DATED PER
 61G15-23.002(1) FAC.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718