| Date |
Text |
| 2008-01-28 09:29:52 | |
| | |
| | |
| | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS,2005 |
| | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, |
| | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THE FOLLOWING COMMENTS ARE REGARDING NOTES AND DRAWING |
| | ON SHEET E2: AND WERE NOT CORRECTLY RESPONDED TO FROM |
| | THE LAST REVIEW. NOTE: FURTHER EXPLANATION OF THE |
| | COMMENTS IS MARKED BY AN ASTERISK. |
| | |
| | 1} 230.2 NUMBER OF SERVICES |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| | ONE SERVICE. INDICATE UNDER WHICH EXCEPTION YOU ARE |
| | ASKING THE AHJ FOR PERMISSION FOR THIS SERVICE.* THIS |
| | COMMENT WAS NOT ADDRESSED, ONLY THE PROPOSED SERVICE IS |
| | SHOWN, NOT THE OTHER SERVICE(S) FOR THE BUILDING. |
| | |
| | 2} INDICATE COMPLIANCE WITH 230.71 MAXIMUM NUMBER OF |
| | DISCONNECTS, AND 230.72 GROUPING OF DISCONNECTS.* SAME |
| | COMMENT AS ABOVE, THE OTHER SERVICE(S) ARE NOT SHOWN |
| | THERREFORE COMPLIANCE WITH THIS ARTICLE CANNOT BE |
| | REVIEWED. |
| | |
| | 4} 250.24(D) GROUNDING ELECTRODE CONDUCTOR- A GROUNDING |
| | ELECTRODE CONDUCTOR SHALL BE USED TO CONNECT THE |
| | EQUIPMENT GROUNDING CONDUCTORS, THE SERVICE-EQUIPMENT |
| | ENCLOSURES, AND, WHERE THE SYSTEM IS GROUNDED, THE |
| | GROUNDED SERVICE CONDUCTOR TO THE GROUNDING |
| | ELECTRODE(S) REQUIRED BY PART III OF THIS ARTICLE. |
| | THERE IS NONE INDICATED ON THE PROPOSED SERVICE. SEE |
| | 250.24(C) FOR POINT OF ATTACHMENT, SEE 250.66 FOR |
| | SIZING REQUIREMENTS.* INDICATING A GROUND ROD ON THE |
| | RISER DIAGRAM DOES NOT MEET THE REQUIREMENT OF THIS |
| | ARTICLE.IF THIS SERVICE IS GROUPED PER 230.72, AND |
| | ALLOWED BY EXCEPTION THEN THE GEC SHALL BE CONNECTED TO |
| | THE EXISTING GEC.PER THIS ARTICLE. |
| | |
| | NEW COMMENT: |
| | |
| | 5} THE ENGINEERS SEAL IS NOT CORRECTLY DATED PER |
| | 61G15-23.002(1) FAC. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |