| Date |
Text |
| 2007-12-20 11:35:54 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | THE FOLLOWING COMMENTS ARE REGARDING NOTES AND DRAWING |
| | ON SHEET E2: |
| | |
| | 1} 230.2 NUMBER OF SERVICES |
| | A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED |
| | BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A) |
| | THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2 |
| | ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND |
| | LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED |
| | TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER |
| | AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING |
| | ONE SERVICE. INDICATE UNDER WHICH EXCEPTION YOU ARE |
| | ASKINGTHE AHJ FOR PERMISSION FOR THIS SERVICE. |
| | |
| | 2} INDICATE COMPLIANCE WITH 230.71MAXIMUM NUMBER OF |
| | DISCONNECTS, AND 230.72 GROUPING OF DISCONNECTS. |
| | |
| | 3}250.6(B) ALTERATIONS TO STOP OBJECTIONABLE |
| | CURRENT- IF THE USE OF MULTIPLE GROUNDING CONNECTIONS |
| | RESULTS IN OBJECTIONABLE CURRENT, ONE OR MORE OF THE |
| | FOLLOWING ALTERATIONS SHALL BE PERMITTED TO BE MADE, |
| | PROVIDED THAT THE REQUIREMENTS OF 250.4(A)(5) OR (B)(4) |
| | ARE MET: SEE ARTICLE FOR MORE CLARIFICATION. THE #8 |
| | GROUND RAN WITH THE SERVICE CONDUCTORS TO THE FIRST |
| | MEANS OF DISCONNECT ARE IN VIOLATION OF THIS ARTICLE |
| | AND MUST BE REMOVED. |
| | |
| | 4} 250.24(D) GROUNDING ELECTRODE CONDUCTOR- A GROUNDING |
| | ELECTRODE CONDUCTOR SHALL BE USED TO CONNECT THE |
| | EQUIPMENT GROUNDING CONDUCTORS, THE SERVICE-EQUIPMENT |
| | ENCLOSURES, AND, WHERE THE SYSTEM IS GROUNDED, THE |
| | GROUNDED SERVICE CONDUCTOR TO THE GROUNDING |
| | ELECTRODE(S) REQUIRED BY PART III OF THIS ARTICLE. |
| | THERE IS NONE INDICATED ON THE PROPOSED SERVICE. SEE |
| | 250.24(C) FOR POINT OF ATTACHMENT, SEE 250.66 FOR |
| | SIZING REQUIREMENTS. |
| | |
| | 5} VERIFY THAT A 3 PHASE SERVICE IS FEEDING A SINGLE |
| | PHASE LOAD. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO |
| | REVIEW COMMENTS IN WRITING. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |