Plan Review Notes For Permit 07090711
Permit Number 07090711
Review Stop E
Sequence Number 2
Notes
Date Text
2007-12-20 11:35:54 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 THE FOLLOWING COMMENTS ARE REGARDING NOTES AND DRAWING
 ON SHEET E2:
  
 1} 230.2 NUMBER OF SERVICES
 A BUILDING OR OTHER STRUCTURE SERVED SHALL BE SUPPLIED
 BY ONLY ONE SERVICE UNLESS PERMITTED IN 230.2(A)
 THROUGH (D). FOR THE PURPOSE OF 230.40, EXCEPTION NO. 2
 ONLY, UNDERGROUND SETS OF CONDUCTORS, 1/0 AWG AND
 LARGER, RUNNING TO THE SAME LOCATION AND CONNECTED
 TOGETHER AT THEIR SUPPLY END BUT NOT CONNECTED TOGETHER
 AT THEIR LOAD END SHALL BE CONSIDERED TO BE SUPPLYING
 ONE SERVICE. INDICATE UNDER WHICH EXCEPTION YOU ARE
 ASKINGTHE AHJ FOR PERMISSION FOR THIS SERVICE.
  
 2} INDICATE COMPLIANCE WITH 230.71MAXIMUM NUMBER OF
 DISCONNECTS, AND 230.72 GROUPING OF DISCONNECTS.
  
 3}250.6(B) ALTERATIONS TO STOP OBJECTIONABLE
 CURRENT- IF THE USE OF MULTIPLE GROUNDING CONNECTIONS
 RESULTS IN OBJECTIONABLE CURRENT, ONE OR MORE OF THE
 FOLLOWING ALTERATIONS SHALL BE PERMITTED TO BE MADE,
 PROVIDED THAT THE REQUIREMENTS OF 250.4(A)(5) OR (B)(4)
 ARE MET: SEE ARTICLE FOR MORE CLARIFICATION. THE #8
 GROUND RAN WITH THE SERVICE CONDUCTORS TO THE FIRST
 MEANS OF DISCONNECT ARE IN VIOLATION OF THIS ARTICLE
 AND MUST BE REMOVED.
  
 4} 250.24(D) GROUNDING ELECTRODE CONDUCTOR- A GROUNDING
 ELECTRODE CONDUCTOR SHALL BE USED TO CONNECT THE
 EQUIPMENT GROUNDING CONDUCTORS, THE SERVICE-EQUIPMENT
 ENCLOSURES, AND, WHERE THE SYSTEM IS GROUNDED, THE
 GROUNDED SERVICE CONDUCTOR TO THE GROUNDING
 ELECTRODE(S) REQUIRED BY PART III OF THIS ARTICLE.
 THERE IS NONE INDICATED ON THE PROPOSED SERVICE. SEE
 250.24(C) FOR POINT OF ATTACHMENT, SEE 250.66 FOR
 SIZING REQUIREMENTS.
  
 5} VERIFY THAT A 3 PHASE SERVICE IS FEEDING A SINGLE
 PHASE LOAD.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS. RESPOND TO
 REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718