| 2007-11-27 11:53:21 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| | FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1.FAC61G15-23.002 REQUIRES THE FOLLOWING: |
| | |
| | C.ALL INFORMATION REQUIRED REGARDING ENGINEER AND |
| | COMPANY (CERTIFICATE OF AUTHORIZATION NUMBER ON EACH |
| | SHEET) |
| | |
| | RESPONSE LETTER STATES THAT THE COFA WAS ADDED. |
| | WHERE? |
| | |
| | THE SEAL, PREVIOUSLY NOT LEGIBLE, STATES "CERTIFICATE". |
| | THIS SEAL HAS BEEN EXPIRED FOR YEARS; THE CURRENT SEAL |
| | STATES "LICENSE" AND FBPE HAS GIVEN THE DIRECTIVE NOT |
| | TO ACCEPT EXPIRED SEALS.PLEASE CONTACT FBPE IF YOU |
| | HAVE QUESTIONS, WWW.FBPE.ORG. |
| | |
| | 2-3.ADDRESSED. |
| | |
| | 4.ITEMS 11 AND 21 STATE THAT NEW GUARDRAIL AND NEW |
| | CHASE AND STAIR WILL BE INSTALLED.PROVIDE |
| | SPECIFICATIONS. |
| | |
| | THE REVISIONS WERE NOT CLOUDED.PLEASE CLOUD ALL |
| | CHANGES AND MARK WITH A REVISION NUMBER SO THAT CHANGES |
| | CAN BE DETERMINED. |
| | THE RESPONSE LETTER STATES "NEW GUARDRAIL AND NEW CHASE |
| | IN STAIRWELL WILL BE INSTALLED . . . "BUT THE |
| | CORRECTION STATED THAT A NEW STAIR WILL BE INSTALLED, |
| | NOT THAT THESE NEW ITEMS WILL BE INSTALLED IN A |
| | STAIRWELL.YOU CANNOT INSTALL ANYTHING IN REQUIRED |
| | PROTECTED EGRESS STAIRS, FBC1019.1.WHERE WILL THE |
| | CHASE BE LOCATED?PLEASE CLARIFY YOUR RESPONSE. |
| | |
| | 5.PROVIDE ROOF PRODUCT APPROVAL, 1-A5.PRODUCT |
| | APPROVALS ARE TO BE REVIEWED BY DESIGNER OF RECORD, |
| | FBC106.3.3. |
| | |
| | ENGINEER'S RESPONSE IS THAT THIS IS AN OUTDATED CODE |
| | REFERENCE AND THERE ARE NO REQUIREMENTS IN THE FBC FOR |
| | PRODUCT APPROVALS.PLEASE SEE FAC9B72.CITY OF WEST |
| | PALM BEACH AMENDMENTS TO THE FBC REQUIRE THAT PRODUCT |
| | APPROVALS BE REVIEWED BY DESIGNER OF RECORD.PRODUCT |
| | APPROVALS ARE REQUIRED FOR ALL COMPONENTS AND CLADDING, |
| | INCLUDING ROOFING.THIS IS COMMON INDUSTRY KNOWLEDGE |
| | IN SOUTH FLORIDA.IT IS POSSIBLE THAT YOUR CONTRACTOR |
| | ASSIST YOU WITH THIS REQUIREMENT.PRODUCT APPROVALS |
| | ARE AVAILABLE AT WWW.FLORIDABUILDING.ORG.THE PRODUCT |
| | APPROVAL WILL BE REQUIRED AT THIS TIME BUT THE OTHER |
| | INFORMATION REQUIRED FOR A ROOFING PERMIT CAN BE |
| | SUBMITTED AT THE TIME OF ROOF PERMIT APPLICATION. |
| | |
| | A SET HAS BEEN RETAINED (PENDING RESOLUTION OF THE |
| | CERTIFICATE OF AUTHORIZATION ISSUE).WHEN |
| | RESUBMITTING, SUBMIT TWO COMPLETE SETS OF PLANS.TO |
| | EXPEDITE PLAN REVIEW, PLEASE SUBMIT A RESPONSE LETTER |
| | STATING HOW EACH ITEM HAS BEEN ADDRESSED. |
| | |
| | PLEASE NOTE THAT I WAS UNABLE TO FIND A CERTIFICATE OF |
| | AUTHORIZATION FOR DELTA GROUPS ENGINEERING, INC. AT |
| | WWW.MYFLORIDALICENSE.COM.CERTIFICATE OF AUTHORIZATION |
| | REQUIRED TO PRACTICE ENGINEERING THROUGH A COMPANY, |
| | FS471.023.IF THE FIRM HAS NOT APPLIED, PLEASE DO SO |
| | AT THIS TIME.IF THE FIRM DOES NOT HAVE A CERTIFICATE |
| | OF AUTHORIZATION, THIS COMPANY CANNOT PRACTICE |
| | ENGINEERING IN FLORIDA (PLANS MUST BE SUBMITTED AND |
| | SEALED INDIVIDUALLY). |
| | |