| 2007-12-20 14:51:23 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME OF THE NOTES FROM PREVIOUS REVIEW |
| | ARE STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | NOTES DUE TO CHANGES MADE TO PLANS WHICH WERE NOT ON |
| | PREVIOUS PLANS. |
| | |
| | |
| | 1) NOTE: PLEASE SEE FBC R313 FOR SMOKE ALARMS REQUIRED |
| | TO MEET NFPA-72 11.5.1.1INSIDE AND OUTSIDE ALL |
| | EXISTING SLEEPING ROOMS. |
| | PLEASE SHOW AND INDICATE THESE IN THE EXISTING DWELLING |
| | EITHER NEW TO BE INSTALLED OR EXISTING MEETING CURRENT |
| | CODE. |
| | THIS NOTE WAS ON PREVIOUS REVIEW. |
| | |
| | 2) NOTE: PLEASE SEE THE RISER DIAGRAM HAS COMPLETELY |
| | BEEN REVISED AND CHANGED FROM PREVIOUS PLANS. |
| | PLEASE SEE THERE ARE SEVERAL ITEMS SHOWN ON LOAD |
| | CALCULATIONS HOWEVER ARE NOT LISTED ON PANEL SCHEDULE. |
| | FOR EXAMPLE: PLEASE SEE DISHWASHER, WASHER, DRYER, |
| | SMALL APPLIANCE, ETC ETC WHICH ARE NOT LISTED ON THE |
| | PANEL SCHEDULE. |
| | PLEASE LIST. |
| | PLEASE KNOW THE MINIMUM OVER CURRENT PROTECTION, AND |
| | CONDUCTOR SIZES NEED TO BE VERIFIED AT THIS TIME FROM |
| | NEW PANEL. |
| | 240.4, 310.16 |
| | PLEASE SEE NEC 408.4 AS THIS REQUIRES ALL CIRCUITS TO |
| | BE IDENTIFIED ON PANEL SCHEDULE FOR ROOMS AND AREAS IN |
| | WHICH THEY FEED. |
| | |
| | 3) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| | CIRCUITS, THE NOTE MENTIONS AT THE BOTTOM OF PANEL |
| | SCHEDULE HOWEVER AS NOTED ABOVE ON NOTE #2, THIS NEEDS |
| | TO BE LISTED FOR CIRCUITS. THIS ITEM COULD BE REDLINED |
| | FOR REVISION BEFORE FINAL HOWEVER MAY BE REVISED AT |
| | THIS TIME. |
| | THIS WAS NOTED ON PREVIOUS REVIEW. |
| | |
| | 4) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE AND |
| | REQUIRED BY CODE ALL RECESSED LIGHTS NEED TO MEET FBC |
| | 13-606.1.ABC.1.2.4 FOR TRANSFER OF AIR FROM CONDITIONED |
| | SPACE. |
| | |
| | ** PLEASE KNOW SOME OF THESE ITEMS COULD HAVE BEEN |
| | RED-LINED HOWEVER NOT ALL. PLANS ARE COMING BACK FOR |
| | COMMENTS FROM ZONING PLEASE ADDRESS AT THIS TIME. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |