| 2007-09-27 07:53:56 | 2007-09-27 07:53:56 |
| | |
| | ** DENIED** |
| | |
| | |
| | 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS |
| | WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES |
| | PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | ** PLEASE KNOW THAT CHANGES FOR NEW CODES IS REQUIRED |
| | FOR ALL TRADES AND FOR ALL REVIEWS EVEN IF COMMENT IS |
| | NOT MADE BY OTHER TRADE(S). |
| | |
| | 2) NOTE: PLEASE SEE THE PLANS ARE MISSING INDICATING |
| | LOCATIONS FOR NEW AND/OR EXISTING SMOKE ALARMS PER FBC |
| | R313 AND NFPA-72 11.5.1.1, 11.8.3. |
| | PLEASE SEE THE FIRST FLOOR OF THE NEW ADDITION IS |
| | MISSING A SMOKE ALARM ALSO IN THE VICINITY LEADING TO |
| | THE FLOOR ABOVE. |
| | PLEASE KNOW THE OFFICE IS CONSIDERED AN ADAPTABLE |
| | SLEEPING ROOM THIS WILL ALSO REQUIRE SMOKE ALARMS |
| | INSIDE AND OUTSIDE THIS ROOM. |
| | PLEASE SEE THE SMOKE DETECTION DEVICE IS REQUIRED TO BE |
| | WITHIN 3FT OG THE PEAK ON THE SLOPED CEILING OR WITHIN |
| | 12INCHES FOR HIGHEST POINT ON FLAT OR TRAY CEILINGS. |
| | PLEASE SEE MINIMUM DISTANCES FROM CEILING FANS AS |
| | STATED IN NFPA-72 11.8.3. |
| | PLEASE KNOW THAT THE PLANS ARE SHOWING *SD* AND LEGEND |
| | STATES SMOKE DETECTORS. PLEASE VERIFY THIS AS BY |
| | NFPA-72 DEFINITIONS A SMOKE DETECTOR IS ONLY A DEVICE |
| | WHICH DETECTS AND DOES NOT SOUND AN ALARM. THE PLANS |
| | WOULD THEN NEED TO INDICATE THE HORN DEVICES ALONG WITH |
| | A FIRE ALARM PANEL. IF THIS IS THE INTENT PLEASE |
| | COMPLETE PLANS ACCORDINGLY. IF THESE ARE MEANT TO BE SA |
| | FOR SMOKE ALARMS WHICH ARE A DEVICE WHICH DETECTS AND |
| | SOUNDS AN ALARM PLEASE ADJUST SYMBOL AND LEGEND. |
| | |
| | 3) NOTE: PLEASE SEE RISER MENTIONS NEW SERVICE, HOWEVER |
| | EXISTING METER. PLEASE INDICATE THE SIZE/AMPERAGE OF |
| | THIS METER. |
| | PLEASE SEE THE RISER IS MISSING ALL CONDUCTORS FROM |
| | METER TO GUTTER, GUTTER TO MAINS ETC. |
| | THIS SERVICE IS BEING SHOWN AS 225AMPS. PLEASE VERIFY. |
| | PLEASE COMPLETE RISER. |
| | 240.4, 310.16 |
| | |
| | 4) NOTE: PLEASE SEE THE PLANS DO NOT INDICATE THE |
| | LOCATIONS OF ALL SERVICE EQUIPMENT ALONG WITH THE |
| | LOCATION OF NEW PANEL. |
| | PLEASE SEE 230.70, 230.71, 230.72, 230.76 AND 230.76 |
| | FOR MAINS AND GROUPING. |
| | PLEASE SEE 110.26, 240.24, FOR LOCATIONS WHICH NEED TO |
| | MEET THESE SECTIONS ALONG WITH OTHER SECTIONS OF THE |
| | NEC. |
| | PLEASE KNOW AS THE LOCATIONS OF EQUIPMENT HAVE NOT BEEN |
| | SHOWN, REVIEW FOR CODE COMPLIANCE CAN NOT BE DONE AT |
| | THIS TIME. |
| | |
| | 5) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR |
| | SIZE IS TOO SMALL FOR THE SERVICE AS SHOWN. |
| | PLEASE SEE 250.66. |
| | |
| | 6) NOTE: PLEASE SEE MISSING COMPLETE GROUNDING |
| | ELECTRODE SYSTEM PER 250.50. |
| | PLEASE SEE MISSING NEW FOOTER STEEL REQUIRED AND OTHER |
| | ELECTRODES. |
| | |
| | 7) NOTE: PLEASE SEE MISSING AIC RATING(S) FOR NEW |
| | SERVICE EQUIPMENT PER 110.9. |
| | FBC 106.1.2 |
| | |
| | 8) NOTE: PLEASE SEE MISSING CONDENSING UNIT ON PLANS |
| | ALONG WITH REQUIRED DISCONNECT PER 440.11 AND MISSING |
| | GFI RECEPTACLE PER 210.63 AND 210.8A3 |
| | |
| | 9) NOTE: PLEASE SEE MISSING REQUIRED LISTED ARC FAULT |
| | PROTECTED CIRCUITS PER 210.12 FOR *ALL* OUTLETS IN |
| | DWELLING SLEEPING ROOMS. |
| | |
| | 10) NOTE: PLEASE SEE MISSING THE REQUIRED DEDICATED |
| | BATH(S) CIRCUIT(S) PER 210.52D AND 210.11C3. PLEASE |
| | KNOW THESE MUST BE 20AMP AND #12. PLEASE ADJUST PANEL |
| | SCHEDULE. |
| | |
| | 11) NOTE: PLEASE SE THE CLOSET LIGHT DOES NOT MEET THE |
| | MINIMUM CLEARANCE REQUIREMENTS PER 410.8. |
| | THIS IS FOR OFFICE CLOSET. |
| | |
| | 12) NOTE: PLEASE 220.83B FOR LOAD CALCULATIONS AND |
| | ADJUST. |
| | PLEASE SEE 422.13 AS THE LOAD TO BE FIGURED FOR THE |
| | WATER HEATER IS TO BE SHOWN AT 125%. THIS WAS CHANGED |
| | IN THE 2005 NEC AS THIS IS NOW CONSIDERED A CONTINUOUS |
| | LOAD. |
| | PLEASE VERIFY SMALL APPLIANCE CIRCUITS PER 210.52B, |
| | 210.11C1, 220.53 (SHOWN AS PORTABLE?) |
| | PLEASE ADJUST LOAD CALCULATIONS. |
| | |
| | 13) NOTE: PLEASE SEE THE RISER IS MISSING THE EQUIPMENT |
| | GROUNDING CONDUCTORS FROM NEW MAIN TO NEW PANEL PER |
| | 250.110, 250.122. |
| | |
| | 14) NOTE: PLEASE SEE 210.52 AS THERE ARE SEVERAL |
| | MISSING RECEPTACLES PER 2FT OF WALL SPACE. SOME OF |
| | THESE LOCATIONS ARE REDLINED ON ONE SET OF PLANS. |
| | PLEASE SEE 2FT, 6FT, AND 12FT RULE. |
| | |
| | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS MISSING FROM |
| | PLANS A FULL AND COMPLETE REVIEW FOR CODE COMPLIANCE |
| | COULD NOT BE DONE AT THIS TIME. PLEASE KNOW THERE MAY |
| | VERY WELL BE NEW COMMENTS ON THE FOLLOWING REVIEW. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |