Plan Review Notes
Plan Review Notes For Permit 07090673
Permit Number 07090673
Review Stop B
Sequence Number 6
Notes
Date Text
2008-10-16 16:54:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC EB FLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FS FLORIDA STATUTE
  
 1. PLEASE EXPLAIN DESIGN PRESSURES SPECIFIED FOR STORM
 PANELS, +-32, AND ROOF DESIGN PRESSURES ON THE PLAN,
 -31.3. IT APPEARS THAT THEY ARE MWRS PRESSURES. STORM
 PANELS SHOULD USE COMPONENT & CLADDING PRESSURES. SEE
 FBC R TABLE 301.2(2). ZONE 3.
  
 2. PLEASE CLARIFY ROOF PITCH, FBC R TABLE 301.2(2).
  
 3. THE INSTALLATION SCHEDULE INCLUDES ONLY ONE OPENING
 AND STATES THAT THIS IS "WORST CASE", 6X7. SEE OTHER
 COMMENTS. THIS MAY BE "WORST CASE" FOR SPAN, BUT IS NOT
 WORST CASE FOR DESIGN PRESSURES. THE ROOF PANELS APPEAR
 TO BE APPROXIMATELY 12SF; EXPOSURE C HAS BEEN DECLARED
 AS WELL AS AN IMPORTANCE FACTOR OF 1. PLEASE REVISE
 INSTALLATION SCHEDULE TO REFLECT CORRECT DESIGN
 PRESSURES.
  
 4. THE PRODUCT APPROVAL FOR THE STORM PANELS WAS NOT
 SUBMITTED. I HAVE PRINTED THIS FOR YOU; HOWEVER, IN THE
 FUTURE, PLEASE BE SURE THAT TWO COPIES OF ALL PRODUCT
 APPROVALS ARE INCLUDED. THE NOA 05-0926.03 IS EXPIRED
 (8/7/2008).
  
 5. ENGINEER HAS SPECIFIED 3 1/2" SHUTTER GLASS
 SEPARATION. BASED ON FIELD CONDITIONS, IS THIS
 POSSIBLE? PLEASE CONTACT ME TO DISCUSS.
  
 6. A 2" EDGE DISTANCE REQUIRES A FACTOR OF .5; SEE
 SHEET 10 OF 15 OF THE NOA. IT IS NOT CLEAR WHICH
 ANCHORS ARE BEING USED; INSTALLATION SCHEDULE SHOULD
 SPECIFY AN ANCHOR WHICH IS INCLUDED IN THE NOA FOR
 ANCHORS INTO CONCRETE. I CANNOT DETERMINE WHETHER OR
 NOT THE FACTOR WAS APPLIED.
  
 7. PLEASE HAVE THE ENGINEER CONFIRM THAT THE STRUCTURE
 CAN ACCOMODATE THE ADDITIONAL WEIGHT OF THE PANELS AND
 THAT THERE WILL NOT BE ANY WATER INTRUSION ISSUES.
 ANCHORS FOR TRACKS ARE TYPICALLY INSTALLED INTO
 CONCRETE, BLOCK, OR WOOD AROUND WINDOW AND DOOR
 OPENINGS. IN THIS CASE, IT APPEARS THAT THE ANCHORS
 WILL BE INSTALLED IN THE METAL STRUCTURE. EMBEDMENT
 REQUIREMENTS FOR ANCHORS INTO ALUMINUM IS NOT CLEAR. IN
 THE CASE OF BLOCK, CONCRETE, AND WOOD, THE ANCHORS DO
 NOT PENETRATE BEYOND THE OPPOSITE SIDE OF THE SUBSTRATE
 FACE.
  
 8. PLEASE CONTACT ME TO DISCUSS ALTERNATE DESIGN
 OPTIONS. CONTRACTOR HAS BEEN TELEPHONED. THIS PROJECT
 WILL BE HELD AT MY DESK FOR THREE BUSINESS DAYS PENDING
 RESOLUTION. A RESUBMITTAL OF REVISED PAPERWORK MAY BE
 SUBMITTED FOR PRELIMINARY REVIEW BY EMAIL,
 [email protected]. ORIGINAL SIGNED, SEALED DOCUMENTS WILL
 BE REQUIRED FOR REVISION ISSUANCE. THANK YOU FOR YOUR
 CONTINUED EFFORTS TO GET THIS MATTER RESOLVED.
  
  
  
  
  
  
  