Plan Review Notes
Plan Review Notes For Permit 07090673
Permit Number 07090673
Review Stop B
Sequence Number 5
Notes
Date Text
2008-07-10 08:21:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE ISSUED PLAN PROVISO AND PREVIOUS LISTS.A
 REVISION FEE IS REQUIRED.A REVISION FEE HAS BEEN
 ADDED.PLEASE NOTE THAT UNDER NORMAL CONDITIONS, THE
 PLAN REVIEW WOULD NOT BE DONE UNTIL ALL FEES HAVE BEEN
 PAID.THIS IS THE SECOND TIME THAT THIS REVISION WAS
 SUBMITTED AS A SUBMITTAL; THEREFORE, TWO REVISION FEES
 HAVE BEEN ADDED.THIS MAY BE PAID ONLINE.PLEASE NOTE
 THAT ONE PRODUCT APPROVAL IS CONSIDERED ONE PAGE FOR
 THE PURPOSE OF REVISION FEES.
  
 2.FBC 301.2.1.2, IMPACT PROTECTION IS REQUIRED.
 PLEASE ALSO SEE STATE OF FLORIDA BUILDING COMMISSION
 DECLARATORY STATEMENT DCA06-DEC-014,
 WWW.FLORIDABUILDING.ORG/UPLOAD/CODEID_2917_DEC014FINAL.
 PDF.THE PLANS AND CALCULATIONS WHICH WERE DESIGNED BY
 MR. DUFFY AND SIGNED AND SEALED BY MR. FISCHER, PE
 STATE THAT IMPACT PROTECTION IS NOT REQUIRED, WHICH
 RENDERS THE PLANS NONCOMPLIANT.PLEASE PROVIDE A
 SIGNED AND SEALED LETTER FROM MR. FISCHER, PE STATING
 THAT IMPACT PROTECTION IS REQUIRED OR REVISE THE PLAN.
 PLEASE CONFIRM THAT BOTH MR. FISCHER AND MR. DUFFY HAVE
 READ THE DECLARATORY STATEMENT.
  
 3.PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF
 RECORD, FBC*106.3.3.THIS MAY BE DONE BY INCORPORATING
 THE PRODUCT APPROVAL NUMBER INTO THE PLAN, SHOP DRAWING
 REVIEW STAMP, OR A LETTER.
  
 4.THE EVALUATION REPORT FOR THE ROOF DECK (FL6909)
 DOES NOT INCLUDE DESIGN PRESSURE LIMITATIONS.SEE PAGE
 1 OF 2, ITEM 4.1, WHICH STATES:
  
 DESIGN: FOR USE IN ALLOWABLE STRESS DESIGN, THE
 ALLOWABLE UNIFORM GRAVITY AND WIND LOADS FOR THE
 ENCLOSURE SYSTEMS ARE DEFINED WITHIN THE ASSOCIATED
 DRAWINGS.
  
 THE DESIGN PRESSURE INFORMATION WHICH IS REQUIRED TO
 DETERMINE CODE COMPLIANCE IS INCLUDED IN OTHER
 DOCUMENTS WHICH ARE AVAILABLE AS A LINK FROM THE
 PRODUCT APPROVAL.PLEASE PRINT ALL DOCUMENTS (FILE
 NAMES END IN PART 1 THROUGH PART 6) AND PROVIDE TWO
 SETS.
  
 5.FL6909, SEE THE PRODUCT APPROVAL DOCUMENT ENDING IN
 PART 2, SHEET 10 OF 38.SEE NOTE 7, MAXIMUM ALLOWABLE
 UPLIFT DUE TO GLASS IS 33PSF.THE ENGINEER HAS
 SPECIFIED 80PSF FOR FIXED WINDOWS AND ROOF PANELS; THE
 PRODUCT APPROVAL APPEARS TO LIMIT THE UPLIFT FOR ROOF
 PANELS TO 33PSF.
  
 6.FL6909, SEE SHEET 15, PRODUCT APPROVAL DOCUMENT
 ENDING IN PART 3.NOTE 4 REFERS TO SHEET 10 NOTE 8,
 BUT NOTES ON SHEET 10 END WITH NOTE 7.IT IS UNCLEAR
 IF THERE IS ADDITIONAL INFORMATION WHICH WOULD BE
 REQUIRED FOR A COMPLETE PLAN REVIEW.
  
 7.FL8697, HORIZONTAL SLIDER WINDOW, PLEASE PROVIDE
 THE DOCUMENTS FROM THE PRODUCT APPROVAL WEBSITE WHICH
 SHOW THE DESIGN PRESSURES.IT APPEARS TO BE +-40PSF,
 BUT THE ENGINEER HAS SPECIFIED -52.5PSF.NOTE THAT THE
 ENGINEER SPECIFIED THIS WINDOW ON THE PLAN BUT AS THIS
 PRODUCT WAS NONCOMPLIANT FOR THE PRESSURES WHICH THE
 ENGINEER HAS SPECIFIED, THE PERMIT WAS ISSUED WITH
 PROVISO.
  
 8.MIAMIDADE NOA06-0911.07, PLEASE INDICATE WHICH
 OPTION YOU ARE USING (SHEET 2) AS THE SILL HEIGHT
 AFFECTS DESIGN PRESSURES FOR THAT PRODUCT.
  
 9.ONLY ONE NUMBER HAS BEEN INDICATED FOR DESIGN
 PRESSURES FOR COMPONENTS AND CLADDING ON THE PLAN;
 THEREFORE THE SAME PRESSURE WOULD APPLY FOR BOTH
 POSITIVE AND NEGATIVE (+-80PSF FOR FIXED, +-52.5 FOR
 SLIDING DOORS AND WINDOWS).SEE THE SLIDING GLASS DOOR
 NOA AND COMMENT 8.WHEN INDICATING WHICH SILL HEIGHT
 OPTION YOU ARE USING, PLEASE CONFIRM THAT THE OPTION
 MEETS BOTH POSITIVE AND NEGATIVE PRESSURES.THIS
 COMMENT APPLIES TO ALL COMPONENTS AND CLADDING.
  
 10. FL251 PGT SLIDING GLASS DOOR PRODUCT APPROVAL WAS
 SUBMITTED WITH NO ASSOCIATED DOCUMENTS (EVALUATION
 REPORT AND INSTALLATION INSTRUCTIONS), AND A LAWSON
 MIAMIDADE NOA WAS ALSO SUBMITTED.IT IS NOT CLEAR
 WHICH PRODUCT YOU PROPOSE TO USE.THE PGT FLORIDA
 STATE PRODUCT APPROVAL HAS MANY DIFFERENT PRODUCTS
 INCLUDED, PRODUCT PROPOSED NOT INDICATED, AND THEREFORE
 WAS NOT REVIEWED.
  
 11.IT APPEARS THAT THE FIXED WINDOWS ARE INCLUDED IN
 THE PRODUCT APPROVAL FOR THE ROOF DECK, FL6909, BUT I
 WAS UNABLE TO LOCATE DESIGN PRESSURES FOR THE GLASS
 WITHIN THE PRODUCT APPROVAL.FLORIDA STATE OR LOCAL
 PRODUCT APPROVAL REQUIRED FOR THE WINDOWS, FAC9B72.
 PLEASE PROVIDE INFORMATION WHICH WILL SHOW COMPLIANCE
 WITH DESIGN PRESSURE REQUIREMENTS SPECIFIED BY THE
 ENGINEER.
  