| 2008-02-15 10:05:36 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.SEE FAC61G15-23.001 REGARDING SEALS ACCEPTABLE TO |
| | THE BOARD.EFFECTIVE JANUARY 1, 2006, A SEAL WHICH HAS |
| | THE WORD "CERTIFICATE" RATHER THAN "LICENSE" IS NO |
| | LONGER ACCEPTABLE.THE NEW REVISED SHEETS ARE NOT |
| | SEALED. |
| | |
| | 2.ALL SHEETS ARE TO CONTAIN A LEGIBLE EMBOSSED SEAL, |
| | FAC61G15-23, FS471. |
| | |
| | 3.SEE PREVIOUS LIST IN REGARDS TO THIS STRUCTURE |
| | BEING PARTIALLY ENCLOSED.THIS COMMENT WAS NOT |
| | ADDRESSED. |
| | |
| | 4.THE ENGINEER HAS SPECIFIED FL6907 FOR THE SLIDING |
| | GLASS DOORS, WHICH HAS A DESIGN PRESSURE LIMITATION OF |
| | +-20.ENGINEER HAS SPECIFIED 52.5 PSF FOR THE SLIDING |
| | GLASS DOORS.PLEASE ADDRESS. |
| | |
| | 5.THE ENGINEER HAS SPECIFIED FL8697 FOR THE HORZONTAL |
| | SLIDING WINDOWS, WHICH HAS A DESIGN PRESSURE LIMITATION |
| | OF +-40.ENGINEER HAS SPECIFIED 52.5 PSF FOR ALL |
| | WINDOWS.PLEASE ADDRESS. |
| | |
| | 6.THE ENGINEER HAS SPECIFIED FL6010 FOR FIXED |
| | WINDOWS.THIS PRODUCT HAS A SIZE LIMITATION OF |
| | 48"X48".SEVERAL OF THE WINDOWS EXCEED THE 48" SPAN |
| | LIMITATION.PLEASE ADDRESS. |
| | |
| | |
| | |