| 2007-12-31 15:39:15 | ****CORRECTIONS**** |
| | |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | 1.A CERTIFICATE OF AUTHORIZATION IS REQUIRED TO |
| | PRACTICE ENGINEERING THROUGH A COMPANY, FS471.023.I |
| | WAS UNABLE TO FIND THE COF A FOR EMC2 STRUCTURAL DESIGN |
| | INC., A FLORIDA CORPORATION.A SET HAS BEEN FORWARDED |
| | TO FBPE. |
| | |
| | 2.THE PLANS STATE THAT IMPACT PROTECTION IS NOT |
| | REQUIRED FBC1609.1.4.NOTE THE FOLLOWING: |
| | |
| | A.THE CORRECT REFERENCE WOULD BE FBC RESIDENTIAL |
| | 301.2.1.2 (ONE AND TWO FAMILY DWELLINGS), NOT FBC 16. |
| | |
| | B.ADDRESSED. |
| | |
| | 3.INCLUDE 2007 AMENDMENTS IN GOVERNING CODE, |
| | EFFECTIVE JULY 1, 2007. |
| | |
| | 4.THE CALCULATIONS ARE TO BE SUBMITTED IN COMPLIANCE |
| | WITH FAC61G15-23.002.NOTE LACK OF REQUIRED |
| | INFORMATION ON EACH SHEET, AND EACH SHEET IS TO BE |
| | SIGNED AND SEALED OR AN INDEX SHEET USED. |
| | |
| | 5.THE ENGINEER HAS DECLARED THIS AS A PARTIALLY |
| | ENCLOSED BUILDING.HOWEVER, SEE THE DEFINITION |
| | FBC1609.2.THIS IS ATTACHED TO THE RESIDENCE, SO IT IS |
| | UNCLEAR HOW THIS IS A PARTIALLY ENCLOSED STRUCTURE. |
| | PLEASE PROVIDE CLARIFICATION/CALCULATIONS. |
| | |
| | 6.THE PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| | DESIGNER OF RECORD, FBC106.3.3. |
| | |