| 2007-10-09 14:11:27 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | ** FBC-2004 WITH 06 REVISIONS CHAPTER 11, FLORIDA |
| | ACCESSIBILITY CODE. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. VALUE OF THE PROPOSED WORK IS TO LOW PER FBC-2004, |
| | CHAPTER 1, SECTION |
| | 108.3, BUILDING PERMIT VALUATION: IF IN |
| | THE OPINION OF THE BUILDING OFFICIAL, |
| | THE CLAIMED VALUATION OF THE BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS |
| | MECHANICAL OR PLUMBING SYSTEMS APPEARS |
| | TO BE UNDERESTIMATED ON THE APPLICATION, |
| | THE PERMIT SHALL BE DENIED. FOR |
| | PERMITTING PURPOSES, VALUATION OF |
| | BUILDINGS AND SYSTEMS SHALL BE TOTAL |
| | REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR |
| | FINISH, NORMAL SITE WORK (EXCAVATION AND |
| | BACKFILL FOR BUILDINGS), ARCHITECTURAL |
| | AND DESIGN FEES, MARKETING COSTS, |
| | OVERHEAD AND PROFIT; EXCLUDING ONLY LAND |
| | VALUE. VALUATION REFERENCES MAY INCLUDE |
| | THE LATEST PUBLISHED DATA OF NATIONAL |
| | CONSTRUCTION COST ANALYSIS SERVICES (MARSHALL-SWIFT, |
| | MEANS ECT.) WITH |
| | REGIONAL ADJUSTMENTS FOR LOCATION AS |
| | PUBLISHED BY INTERNATIONAL CODE |
| | CONGRESS. |
| | NOTE: ONLINE SEARCH OF PEDICURE CHAIRS INDICATES COST |
| | PER ONE CHAIR AT $2100.00 NOT TO MENTION THE COST OF |
| | THE KITCHEN SINK AND WATER HEATER PLUS LABOR AND |
| | MATERIALS. ADJUST THE COST AND PAY THE DIFFERENCE PRIOR |
| | TO THE RESUBMITTAL. |
| | |
| | 2. SUBMIT (TWO COPIES) OF MINIMUM OF 1/8 INCH SCALE OF |
| | THE EXISTING FLOOR PLAN LAYOUT OF BUILDING AND ANOTHER |
| | WITH THE PROPOSED LAYOUT OF THE PEDICURE CHAIRS AND |
| | KITCHEN SINK PER FBC-2004 CHAPTER 1, SECTION 106.1.3. |
| | |
| | 3. NEW PROPSED KITCHEN SINK NEEDS TO BE ACCESSIBLE AND |
| | AN ELEVATION DETAIL IS REQUIRED WITH THE FOLLOWING |
| | INFORMATION: |
| | |
| | **SINKS |
| | A} 11-4.24.2 HEIGHT: 34 INCHES MAX TO RIM. |
| | B} 11-4.24.3 KNEE CLEARANCE: 27 INCHES HIGH, 30 INCHES |
| | WIDE, 19 INCHES DEEP. |
| | C} 11-4.24.4 SINK DEPTH: 6-1/2 INCHES DEEP. |
| | D} 11-4.24.5 CLEAR FLOOR SPACE: 30 INCHES X 48 INCHES. |
| | (INDICATE CLEAR FLOOR SPACE ON PROPOSED LAYOUT FLOOR |
| | PLAN) |
| | E} 11-4.24.6 EXPOSED PIPES AND SURFACES: PROTECTION |
| | REQUIRED. |
| | F} 11-4.24.7 FAUCETS: LEVER-OPERATED, PUSH-TYPE, |
| | TOUCH-TYPE, OR ELECTRONICALLY CONTROLLED ARE |
| | ACCEPTABLE. |
| | |
| | 4. PER FBC-2004 CHAPTER 1, SECTION106.3.5.1.3 PLEASE |
| | INDICATE THE FOLLOWING INFORMATION PER THE FOLLOWING |
| | SUBSECTIONS: |
| | |
| | (3) ISOMETRIC WATER RISER DIAGRAM INDICATING PIPE |
| | SIZES, VALVE LOCATIONS, BACKFLOW PREVENTION (BACKFLOW |
| | PREVENTOR LOCATION AND VACUUM BREAKERS FOR NEW PEDICURE |
| | CHAIRS) |
| | |
| | (5) WATER HEATER SIZE AND LOCATION ON FLOOR PLAN. |
| | |
| | (8) BACKFLOW PREVENTER LOCATION ON SITE PLAN. |
| | |
| | (10) LOCATION OF THE WATER SUPPLY LINE. |
| | |
| | 5. CLEARLY INDICATE ON THE RESUBMITTED PLANS THAT THE |
| | PROPOSED AIR ADMITTANCE VALVES ARE COMPLIANT WITH |
| | FBC-2004 WITH 05 & 06 REV. SECTION 917.3.1 LOCATION OF |
| | BRANCH: THE HORIZONTAL BRANCH DRAIN SHALL CONNECT TO |
| | THE DRAINAGE STACK OR BUILDING DRAIN A MAXIMUM OF FOUR |
| | BRANCH INTERVALS FROM THE TOP OF THE STACK. |
| | |
| | 6. 1. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| | THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| | THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| | NAME, AND ALSO DATE DRAWING. PLEASE DO |
| | THIS PRIOR TO RESUBMITTING. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |