| 2007-10-15 16:49:44 | **** DENIED **** |
| | |
| | |
| | |
| | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT |
| | CODES ARE STATED ON PLANS. |
| | PLEASE KNOW THAT ALL PERMIT APPLICATIONS DATED AFTER |
| | DECEMBER 8TH, 2006 FALL UNDER THE FOLLOWING CODES AT A |
| | MINIMUM. |
| | PLEASE BE AWARE OF ANY OTHER CODES WHICH MAY BE |
| | REFERENCED BY OTHER TRADES DURING THEIR REVIEW. THE |
| | FOLLOWING IS NEEDED ON ELECTRICAL SHEETS AS WELL AS |
| | FIRE ALARM SHEETS BY THIS REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS. |
| | 2005 NFPA-70 |
| | |
| | 2) NOTE: PLEASE SEE THE SEAL WHICH IS BEING USED BY THE |
| | ENGINEER IS NO LONGER VALID IN THE STATE OF FLORIDA. |
| | PLEASE SEE RULING DATED FEBRUARY OF 2004 WHICH REQUIRED |
| | ALL SEALS FOR ENGINEERS WITH THE WORDING OF |
| | *CERTIFICATE* TO BE CHANGED TO *LICENSE*. |
| | 61G15-23.001. |
| | PLEASE KNOW AN EXTENSION WAS GIVEN TO A DATE OF |
| | DECEMBER 31ST, 2005 HOWEVER PLANS MAY NOT USE THIS SEAL |
| | AFTER THIS DATE. ANY QUESTIONS SHOULD BE DIRECTED TO |
| | THE FLORIDA BOARD OF PROFESSIONAL ENGINEERS AS THIS |
| | RULING WAS CHANGED OVER THREE YEARS AGO. |
| | PLEASE OBTAIN NEW SEAL AND ADJUST FOR NOTES #2 AND #3. |
| | |
| | 3) NOTE: PLEASE SEE FS 471.025 AS THIS AND FAC |
| | 61G15-23.002 REQUIRES THE ENGINEER TO DATE PLANS WHEN |
| | SIGNING AND SEALING DOCUMENTS. THE PLANS WERE NOT |
| | DATED. |
| | |
| | 4) NOTE: PLEASE SEE THE EQUIPMENT AS SUBMITTED AND |
| | SHOWN ON PLANS DO NOT INDICATE ANY LISTING FROM A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY. NRTL. |
| | PLEASE SEE 110.3, 90.7 |
| | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR |
| | REVIEW. |
| | THIS IS FOR EQUIPMENT ON A-2.3 |
| | |
| | 5) NOTE: PLEASE BE SURE TO PROVIDE ELECTRICAL |
| | INFORMATION FOR EQUIPMENT ON SHEETS FOR VOLTAGE |
| | CONNECTIONS. |
| | PANEL IS BEING NOTED AS 277/480V AND UNTIL MANUFACTURES |
| | SPECS/CUT SHEETS CAN BE REVIEWED SIZING OF CIRCUITS, |
| | LOADS ETC CAN NOT BE CONFIRMED. |
| | ELECTRICAL PLANS DO NOT INDICATE SIZE OF CIRCUITS, OVER |
| | CURRENT PROTECTION, CONDUCTOR ETC.240.4, 310.16 ETC |
| | PLAN SHEET A-1.1 SHOWS ONE NEW RECEPTACLE BEING |
| | INSTALLED WHICH DOES NOT SEEM TO BE WHAT IS NEEDED |
| | BASED ON EQUIPMENT AS SHOWN. IS THIS A 277/480V |
| | RECEPTACLE? PLEASE SPECIFY TYPE. (NEMA RATING/NUMBER). |
| | ELECTRICAL PANEL SCHEDULE DOES NOT SHOW THE NEW |
| | CIRCUIT(S). 408.4 |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | |
| | |
| | ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL |
| | AFFECT PLANS, SUBMITTED DOCUMENTS AND ELECTRICAL |
| | PLANS. |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |