| Plan Review Notes For Permit 07090655 |
| Permit Number |
07090655 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2007-10-05 12:10:46 | ***DENIED*** | | | | | | 1) DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | LOCATION, NATURE AND EXTENT OF WORK. 106.1.1. PLEASE | | | CLEARLY ILLUSTRATE ALL DEVICES NEW OR EXISTING. | | | | | | 2) IF THIS IS CONSIDERED A NEW FIRE ALARM SYSTEM THAT | | | SUPERVISES AN AUTOMATIC FIRE SPRINKLER SYSTEM, THE FIRE | | | ALARM IS REQUIRED TO BE UL CERTIFIED FOR CENTRAL | | | STATION SERVICE. | | | | | | 3) PREVIOUS PLANS SUBMITTED SHOWED VISUAL DEVICES IN | | | ADDITION TO AUDIBLE. THIS IS NOT CLEARLY SHOWN ON THIS | | | SUBMITTAL. | | | | | | 4) FIRE ALARM RISER INDICATES AN "F" BUT THIS IS NOT | | | SHOWN ON THE LEGEND? | | | | | | 5) FIRE ALARM SYSTEMS SHALL BE CLASS A OR FULLY | | | ADDRESSABLE. | | | | | | 6) THE LETTERS C AND K ARE SHOWN ON DRAWINGS. PLEASE | | | EXPLAIN. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|