| Date |
Text |
| 2008-04-18 18:21:30 | ** DENIED 4TH AUDIT ** |
| | |
| | |
| | ** PLEASE SEE NEW COMMENTS FOR AUDIT DUE TO COMPLETELY |
| | NEW DOCUMENTS NOW SUBMITTED WHICH ARE NOT THE SAME AS |
| | PREVIOUS SUBMITTED DOCUMENTS. |
| | PLEASE SEE NOTES BELOW. THESE ARE REQUIRED BY FLORIDA |
| | STATUES AND SHALL CORRECTED AND COMPLETE BEFORE PERMIT |
| | MAY BE ISSUED. |
| | |
| | 1) NOTE: PLEASE BE SURE TO SUBMIT ALL DOCUMENTS INTO |
| | TWO SETS. PLEASE DO NOT SUBMIT ALL DOCUMENTS INTO ONE |
| | BOOK. |
| | FBC 106.1.3, 106.1. ADMIN SECTION OF THE FLORIDA |
| | BUILDING CODE FOR COORDINATION OF PLANS AND DOCUMENTS. |
| | |
| | 2) NOTE: PLEASE KNOW THE TWO SUBMITTED *NOTICE TO |
| | BUILDING OFFICIAL* LETTERS AS REQUIRED PER FS 553.791 |
| | ARE BOTH IN FACT *COLORED PHOTO-COPIES* AND ARE NOT |
| | ORIGINAL. |
| | PLEASE KNOW THAT ORIGINALS NOTARIZED AND COORDINATED |
| | WITH THE PLAN REVIEW AFFIDAVITS WILL BE REQUIRED. |
| | |
| | 3) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED |
| | DO NOT CONTAIN ANY REQUIRED STAMPS OR SIGNATURES BY THE |
| | PRIVATE PROVIDER AS REQUIRED PER FS 553.791. PLEASE BE |
| | SURE TO SUBMIT NEW ENERGY CALCULATIONS TO THE PRIVATE |
| | PROVIDER TO REVIEW FOR CODE COMPLIANCE WITH REVISED |
| | PLANS. |
| | PLEASE BE SURE THESE ARE COORDINATED WITH ALL SUBMITTED |
| | DOCUMENTS AND SUBMIT TWO COMPLETED NEW SETS OF ENERGY |
| | CALCULATIONS FOR MINIMUM DOCUMENTS REQUIRED PER FBC |
| | 106.1 |
| | |
| | 4) NOTE: PLEASE SUBMIT TWO COMPLETE SETS OF PLANS |
| | SHOWING THE ACCURATE SCOPE OF WORK. PLANS/SETS ARE NOT |
| | COMPLETE AND ARE MISSING SHEET(S). |
| | PLEASE SEE ONE SET CONTAINS A SHEET E2.2 WHICH WAS |
| | SIGNED, DATED AND SEALED BY THE ELECTRICAL ENGINEER ON |
| | 2/21/08. THIS SHEET ON ONE OF THE SETS IS STILL SHOWING |
| | THE OUTSIDE ROOF COVERED EATING AREA WHICH IS NOT ON |
| | OTHER SHEETS IN SETS. |
| | PLEASE KNOW THAT THIS SHEET E2.2 IS NOT REVISED NOR IS |
| | THERE A SHEET E2.2 IN THE FIRST REVISED SET. THIS OTHER |
| | SET IS MISSING SHEET E2.2 ALL TOGETHER. COVER SHEET |
| | T1.1 CLEARLY STATES THERE SHOULD BE AN E2.2 IN BOTH |
| | SETS. BOTH SHOULD BE REVISED TO ACCURATELY DEPICT THE |
| | LATEST REVISED FLOOR PLANS ALONG WITH ELECTRICAL SCOPE |
| | OF WORK. |
| | PLEASE ALSO SEE ONE SET IS MISSING SHEET E5.1 WHICH IS |
| | ALSO SHOWN ON COVER SHEET T1.1. THE SECOND SET DOES |
| | CONTAIN THIS SHEET E5.1 WHICH WAS SIGNED, SEALED AND |
| | DATED 2-21-08. |
| | ** PLEASE COORDINATE ALL PLANS AND DOCUMENTS. |
| | |
| | 5) NOTE: PLEASE SEE FLORIDA STATUTES 471.025 AND |
| | FLORIDA ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES |
| | THE DESIGNER OF RECORD TO SIGN, DATE AND SEAL ALL PLANS |
| | RELEVANT TO THAT LICENSED DESIGNERS SCOPE OF WORK. |
| | PLEASE SEE THE REVISED ELECTRICAL SHEETS ARE NOW COMING |
| | IN WITH A COMPLETELY NEW SIGNATURE THAN THOSE SHOWN ON |
| | PREVIOUS PLANS AS WELL AS SOME OF THE SHEETS IN THESE |
| | SETS ALSO DO NOT CORRELATE. |
| | THIS NEW SIGNATURE DOES NOT COORDINATE WITH THE |
| | SIGNATURE GIVEN TO THIS OFFICE ON PREVIOUS PROJECTS BY |
| | SIGNATURE VERIFICATION LETTER WHICH WAS SIGNED, DATED, |
| | SEALED AND NOTARIZED. ALL SHEETS AND DOCUMENTS WILL NOW |
| | BEE RETAINED BY THIS REVIEWER. THIS OFFICE MAY HAVE NO |
| | CHOICE BUT TO TURN SAID PLANS AND DOCUMENTS OVER TO THE |
| | FLORIDA BOARD OF ENGINEERS FOR REVIEW. |
| | THE DESIGNER OF RECORD MAY APPEAR IN PERSON WITH PHOTO |
| | IDENTIFICATION TO SIGN, DATE AND SEAL REVISED PLANS |
| | WHICH WILL BE NEEDED AS CURRENT SHEETS ARE BEING |
| | RETAINED BY THIS OFFICE. |
| | |
| | 6) NOTE: PLEASE SEE THE PRIVATE PROVIDER INFORMATION |
| | LISTED ON THE NOTICE TO BUILDING OFFICIAL AND PRIVATE |
| | PROVIDER AFFIDAVIT DOES NOT CORRELATE. THE NOTICE TO |
| | BUILDING OFFICIAL STATES MR. MORGAN DICKINSON P.E. WITH |
| | AN ADDRESS LOCATED TAMPA, FLORIDA. HOWEVER THE PRIVATE |
| | PROVIDER AFFIDAVITS STATE THE PRIVATE PROVIDER AS MR. |
| | OSVALDO AREVALO P.E.. |
| | PLEASE COORDINATE ALL DOCUMENTS AND INFORMATION. FS |
| | 553.791 |
| | FBC 106.1, 106.3.5 ADMIN SECTION OF THE FLORIDA |
| | BUILDING CODE FOR MINIMUM CONSTRUCTION DOCUMENTS |
| | REQUIRED AND COORDINATION OF INFORMATION. |
| | |
| | 7) NOTE: PLEASE BE SURE THE JURISDICTION AS LISTED ON |
| | THE COVER OF THE ENERGY CALCULATIONS ACTUALLY LISTS THE |
| | JURISDICTION IN WHICH THE SCOPE OF WORK IS TAKING |
| | PLACE. |
| | PLEASE SEE THESE SHEETS LIST PALM BEACH COUNTY AND NOT |
| | THE CITY OF WEST PALM BEACH. |
| | 13-400.3.B, 13-415.2 |
| | FBC 106.1, 106.3.5 FOR COORDINATION OF CONSTRUCTION |
| | DOCUMENTS AND PLANS FOR RECORD. |
| | |
| | 8) NOTE: PLEASE SEE ALL THREE PREVIOUS AUDITS WITH |
| | RESPECT TO THE LIGHTING ON PLANS WHICH NEED TO |
| | COORDINATE WITH THE SUBMITTED INPUT DATA REPORT ON THE |
| | ENERGY CALCULATIONS. |
| | 13-400.3.B, 13-415.2, 13-415.2.ABC.1.1, .1.2, .1.3. THE |
| | BELOW IS ONCE AGAIN SOME EXAMPLES OF LIGHTING WHICH IS |
| | LOCATED ON PLANS AND LISTED ON FIXTURE LEGEND WHICH ARE |
| | NOT IN THE IDR. THIS IS NOT AN EXHAUSTED LIST OF ALL |
| | LIGHT FIXTURES WHICH MAY NOT COORDINATE. THE AUDIT IS |
| | TO SHOW WHERE MINIMUM CODE COMPLIANCE IS NOT MET AND |
| | EXAMPLES ARE GIVEN AS A BENEFIT ONLY. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR. THERE ARE |
| | FIXTURE LOCATIONS FOR TYPE NN FIXTURES ON WEST |
| | ELEVATION; THE COUNT ON PLANS IS THE SAME AS THE IDR |
| | HOWEVER THE VA RATING USED IN THE IDR IS LOWER THAN |
| | THAT STATED ON THE FIXTURE LEGEND. THE NN FIXTURE IS |
| | LISTED AS 50W ON LEGEND HOWEVER WITH 75W BALLAST. THE |
| | SHEET A2.2 WHICH IS REFERENCED IN NOTE #1 ON LIGHTING |
| | LEGEND SPECIFICALLY MENTIONS TO SEE ARCHITECTURAL PLANS |
| | FOR ACTUAL FIXTURES AND LOCATIONS. IF YOU GO TO SHEET |
| | A2.2 THE SHEET DOES SHOW FIXTURES *NN* HOWEVER THE |
| | ARCHITECT?S FIXTURE LEGEND SPECIFICALLY STATES THE *NN* |
| | FIXTURES ARE * NOT USED*. ONCE AGAIN AS STATED ON |
| | PREVIOUS REVIEW PLEASE COORDINATE ALL LIGHTING ON |
| | ARCHITECTURAL PLANS WITH THAT OF THE LIGHTING AND |
| | FIXTURES ON ELECTRICAL PLANS. THE PREVIOUS REVIEWS |
| | SPECIFICALLY GAVE CODE SECTIONS 13-415.2.ABC.1.1, .1.2 |
| | AND .1.3. |
| | THE MINIMUM INPUT REQUIRED INTO THE IDR IS THAT IF THE |
| | BALLAST OUTPUT, MAXIMUM FIXTURE VA RATING ETC. THIS IS |
| | NOT THE VA OR WATTAGE OF BULB INSTALLED IS IT THE |
| | MAXIMUM RATING OF A FIXTURE OR THE BALLAST OUTPUT. AN |
| | EXAMPLE WAS GIVEN ON PREVIOUS REVIEW. |
| | FOR EXAMPLE: |
| | PLEASE SEE THE FIXTURE LEGEND WHICH SHOWS TYPE *QQ* |
| | FIXTURES FOR EXTERIOR. WHAT ARE THESE? DOES THE PLANS |
| | OR IDR CONTAIN A MISPRINT? IF SO PLEASE ALSO SEE THE |
| | TYPE *QQ* FIXTURES LISTED AS EXTERIOR SCONCES ARE |
| | 100W/VA FIXTURES. THESE SAME FIXTURE ARE NOTED AS NOT |
| | USED ON SHEET A2.2 SO PLANS AND IDRDO NOT |
| | COORDINATE. |
| | FOR EXAMPLE: |
| | AS NOTED ABOVE FOR FIXTURES *NN* ON ARCHITECTURAL SHEET |
| | A2.2 WHICH WERE NOT SHOWN OR LABELED AS *NOT USED* |
| | PLEASE ALSO SEE THERE ARE SEVERAL FIXTURES ON |
| | ELECTRICAL LIGHTING PLANS SHEET E1.1 WHICH ARE NOT |
| | LOCATED ON SHEET A2.2. SOME OF THESE ARE FIXTURES SUCH |
| | AS EM8 AND EM4 ARE ON ELECTRICAL HOWEVER NOT ON |
| | ARCHITECTURAL. |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |