| Date |
Text |
| 2008-03-08 10:48:55 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODES WPB |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | ******FROM PREVIOUS REVIEWS: (3RD REVIEW) |
| | |
| | 1. OK |
| | 2. OK |
| | |
| | 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED |
| | INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED |
| | NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| | THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN |
| | SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED, |
| | SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE |
| | LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC |
| | 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219, |
| | 481.2055. |
| | ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED |
| | LETTER HAS NOT BEEN SUBMITTED AS REQUESTED. |
| | ******RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED |
| | LETTER HAS NOT BEEN SUBMITTED AS REQUESTED. |
| | |
| | |
| | 4. OK |
| | 5. OK |
| | 6. OK |
| | |
| | 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE |
| | REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION |
| | 611.1. |
| | ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR |
| | THE WATER FILTER HAVE NOT BEEN FOUND. ******RESPONSE |
| | NOTED, BUT THE MANUF. SPECIFICATIONS FOR THE WATER |
| | FILTER DO NOT SHOW COMPLIANCE/CERTIFICATION FOR NSF-42. |
| | THE REQUIREMENTS FOR NSF-42 ARE A REQUIREMENT FOR |
| | REDUCTION OF CHLORINE, TASTE & ODOR, CHLORAMINE, ZINC |
| | ETC AS WELL AS BACTERIOSTATIC EFFECTS. NSF-53 IS NOT |
| | SHOWN TO COMPLY WITH THE REQUIREMENTS OF NSF-42. A |
| | SEPARATE FILTER CAN BE ADDED TO THE SYSTEM TO COMPLY |
| | WITH THE REQUIREMENTS OF SECTION 611.1 |
| | |
| | 8. OK |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | 21. OK |
| | |
| | 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED: |
| | |
| | A. OK |
| | B. OK |
| | C. OK |
| | D. OK |
| | E. OK |
| | F. OK |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS |
| | FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE |
| | RH UNITS. |
| | ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT |
| | SUBMITTED. |
| | ******RESPONSE NOTED, BUT THE RICE COOKER IS NOT LISTED |
| | AS BEING TESTED FOR THE GAS COMPONETS. THE ONLY LISTING |
| | SHOWN IS FOR NSF. PER SECTION 301.3. PLEASE SHOW |
| | LISTING. |
| | |
| | H. OK |
| | 23. OK |
| | |
| | 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE |
| | DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED |
| | ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE |
| | NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE |
| | FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY |
| | HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS |
| | NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE |
| | CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE |
| | RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4. |
| | ******RESPONSE NOTED, BUT THE VENT FOR THE FLOOR SINK |
| | INDICATED IN COMMENT ABOVE DOES NOT COMPLY WITH CODE |
| | SECTION 905.4. FLOOR SINK CAN BE CONNECTED ON THE RISE |
| | OF THE VENT TO WASH THE BASE OF THE VENT. |
| | |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE |
| | OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS |
| | 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND |
| | APPLICATION FOR PERMIT. |
| | ******RESPONSE NOTED, BUT THE LETTER HAS NOT BEEN |
| | SUBMITTED. |
| | |
| | 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1C. THE GAS SYSTEM IS NOW INDICATED AS A 2PSI SYSTEM. |
| | REGULATORS ARE REQUIRED IN THE SYSTEM TO REDUCE THE |
| | PRESSURE FROM 2PSI TO .5 PSI PRIOR TO EACH APPLIANCE OR |
| | GROUP OF APPLIANCES. A SHUT OFF VALVE IS REQUIRED |
| | UPSTREAM OF EACH REGULATOR WITH A UNION DOWNSTREAM OF |
| | THE SHUT OFF VALVE. SECTION 409.4. (SHUT OFF VALVES, |
| | REGULATORS & UNIONS CAN NOT BE LOCATION IN THE |
| | CEILING). |
| | |
| | 2C. SUBMIT MANUF. SPECIFICATIONS FOR THE GAS |
| | REGULATORS. IF THERE ARE VENT LINES ON THE REGULATORS, |
| | INDICATE MATERIAL FOR VENTS. (NO COMBUSTABLE MATERIALS |
| | FOR THE VENTS). SHOW ROUTING AND TERMINATION OF VENTS |
| | IF INSTALLED/REQUIRED. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE |
| | VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |