| Date |
Text |
| 2008-01-28 16:53:59 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODES WPB |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | |
| | 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED |
| | BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT, |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| | (561) 822-2272, E-MAIL [email protected] OR CALVIN |
| | WILLIAMS (561) 822-2284, E-MAIL [email protected]. |
| | THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN |
| | DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL |
| | BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR |
| | EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL |
| | CODE ARTICLE III SECTION 90-124(7). |
| | ****RESPONSE NOTED, BUT THE WRITTEN APPROVAL HAS NOT |
| | BEEN SUBMITTED. |
| | |
| | 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED |
| | INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED |
| | NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| | THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN |
| | SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED, |
| | SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE |
| | LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC |
| | 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219, |
| | 481.2055. |
| | ****RESPONSE NOTED, BUT THE SIGNED, SEALED, NOTORIZED |
| | LETTER HAS NOT BEEN SUBMITTED AS REQUESTED. |
| | |
| | 4. OK |
| | |
| | 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR |
| | THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV. |
| | SECTIONS 303, 303.1 303.2, & 303.4. |
| | ****RESPONSE NOTED, BUT THE LAV DRAIN PAN AND GRANITE |
| | LAV SHALL BE SUBMITTED AS ALTERNATIVE MATERIALS, DESIGN |
| | & METHODS OF CONSTRUCTION AND EQUIPMENT PER SECTION |
| | 104.1.1 SUBMIT DETAILS AS TO THE FINISH AND POROSITY OF |
| | THE GRANITE AND INDICATE THE GUAGE OF THE STAINLESS |
| | STEEL LAV DRAIN PAN. INFORMATION SHALL BE SUBMITTED TO |
| | THE BUILDING OFFICIAL. |
| | |
| | 6. OK |
| | |
| | 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE |
| | REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION |
| | 611.1. |
| | ****RESPONSE NOTED, BUT THE MANUF. SPECIFICATIONS FOR |
| | THE WATER FILTER HAVE NOT BEEN FOUND. |
| | |
| | 8. OK |
| | 9. OK |
| | |
| | 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163 |
| | DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES |
| | DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | ****RESPONSE NOTED, BUT THE KITCHEN SPEC BOOK HAS NOT |
| | BEEN FOUND. |
| | |
| | 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN |
| | DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR |
| | RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED |
| | BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION |
| | 106.1. |
| | ****RESPONSE NOTED, BUT THE KITCHEN CONSULTANT RESPONSE |
| | HAS NOT BEEN FOUND. |
| | |
| | 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND |
| | THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE |
| | TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL |
| | BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR |
| | FILES. FAC 61G15-23.002(2) & FS 471.025. ****RESPONSE |
| | NOTED, BUT THE SIGNED, SEALED, NOTORIZED LETTER HAS NOT |
| | BEEN SUBMITTED. |
| | |
| | 13. OK |
| | 14. OK |
| | 15. OK |
| | 16. OK |
| | 17. OK |
| | 18. OK |
| | 19. OK |
| | 20. OK |
| | |
| | 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER |
| | SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO |
| | 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE |
| | GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED. |
| | SECTION 402. |
| | ****RESPONSE NOTED, BUT THE INLET PRESSURE HAS BEEN |
| | INDICATED AS 2PSI AND .5 PSI. PLEASE CONTACT THE GAS |
| | PROVIDER AND INDICATE PRESSURE PROVIDED AT THE METER. |
| | |
| | 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT |
| | INDICATED. |
| | ****RESPONSE NOTED, BUT THE CUT SECTIONS FROM THE METER |
| | TO THE FIRST RISERS ON BOTH BRANCHES HAVE NO LENGTHS |
| | INDICATED AS WELL AS THE LENGTH FROM THE BRANCH LINES |
| | TO THE PATIO HEATERS. |
| | |
| | B. OK |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE |
| | REQUIREMENT "A" IS ADDRESSED. |
| | ****RESPONSE NOTED, BUT "A" HAS NOT BEEN COMPLETLY |
| | ADDRESS AND THE TOTAL DISTANCE FROM THE METER TO THE |
| | MOST REMOTE OUTLET DOES NOT APPEAR TO BE CORRECT. |
| | PLEASE RECHECK THE ADDITION. |
| | |
| | D. OK |
| | |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT |
| | #21. |
| | ****RESPONSE NOTED, BUT THE DELIVERY PRESSURE CAN BE |
| | 2PSI OR .5 PSI, BUT NOT BOTH. INDICATE THE DELIVERY |
| | PRESSURE. |
| | |
| | F. OK |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS |
| | FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE |
| | RH UNITS. |
| | ****RESPONSE NOTED, BUT MANUF. SHEETS ARE NOT |
| | SUBMITTED. |
| | |
| | H. OK |
| | |
| | 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR |
| | 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2" |
| | REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE |
| | RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE |
| | 402.4(2) - (IF SCHEDULE 40 PIPE). |
| | ****RESPONSE NOTED, BUT 3/4" IS STILL SHOWN TO THE RICE |
| | COOKERS. |
| | |
| | 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE |
| | DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED |
| | ON BOTH VENT LINES. (SEE ATTACHED SHEET). ****RESPONSE |
| | NOTED, BUT THE RISER DIAGRAM STILL DOES NOT REFLECT THE |
| | FLOOR PLAN, NOR DOES IT MEET CODE. THERE IS A DRY |
| | HORIZONTAL VENT UPSTREAM OF FS3 FOR FIXTURE 63. THIS IS |
| | NOT SHOWN ON THE FLOOR PLAN. ALSO FS1 FOR THE |
| | CONDENSATE FROM THE WALK IN COOLER IS NOT SHOWN ON THE |
| | RISER DIAGRAM. SECTIONS 106.1.1, 905.3 & 905.4. |
| | |
| | 25. OK |
| | 26. OK |
| | 27. OK |
| | 28. OK |
| | |
| | **********NEW COMMENTS********** |
| | |
| | 1B. ALL PRIVATE PROVIDER AFFIDAVIT PROJECTS REQUIRE THE |
| | OWNER TO SIGN AN OWNER ACKNOWLEDGEMENT LETTER PER FS |
| | 553.791. THIS SHALL BE SUBMITTED WITH THE PLANS AND |
| | APPLICATION FOR PERMIT. |
| | |
| | 2B. SEE ATTACHED SHEET CONCERNING THE DESIGN |
| | PROFESSIONAL AND FS 553.80(2)(B). THIS IS GIVEN AS A |
| | NOTICE ONLY AT THIS TIME. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | ****NO RESPONSE OF THE REQUEST FOR ONE COPY OF THE |
| | VOIDED SHEETS TO BE SUBMITTED FOR COMPARISON. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |