| Date |
Text |
| 2008-01-31 15:27:03 | ** NOTE ADDED ** |
| | 1/31 |
| | |
| | |
| | 1) NOTE: IT HAS BEEN CONFIRMED WITH FIRE MARSHAL THAT |
| | AN EXIT SIGN WILL BE REQUIRED AT DELIVERY DOOR FOR |
| | KITCHEN PERSONNEL. |
| | LS 101 7.8,7.9 |
| 2008-01-30 14:58:50 | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM |
| | PREVIOUS REVIEW WHICH ARE IN NEED OF ADDRESSING. |
| | |
| | 1) NOTE: PLEASE SUBMIT THE REQUIRED FEE OWNER AFFIDAVIT |
| | WHICH IS REQUIRED PER FS 553.791(4)(C). |
| | |
| | 2) NOTE: PLEASE SEE SIGNATURE LETTER SUBMITTED FOR THE |
| | ENGINEER CONTAINS TWO DIFFERENT SIGNATURES OF THE |
| | RESPONSIBLE ENGINEER OF RECORD. |
| | PLEASE SEE FS 471.025 WHICH SIGNATURE IS THE LEGAL |
| | ORIGINAL SIGNATURE FOR ENGINEER OF RECORD? |
| | PLEASE CALL TO GO OVER. |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW NOTE #17 WITH |
| | RESPECT TO LIGHTING ON BATH ROOMS BEING NOTED TO BE |
| | CONTROLLED BY DIMMING PANEL. THE RESPONSE WAS THE |
| | EMERGENCY LIGHT FIXTURE IS CIRCUITED TO THE HOT/LINE |
| | SIDE OF THE LOCAL CIRCUIT WHICH IS OK. PLEASE SEE THE |
| | PREVIOUS REVIEW COMMENT WAS NOT FOR THE EMERGENCY |
| | LIGHTING AND CIRCUITING, IT WAS FOR THE LEVELS OF |
| | LIGHTING UNDER NORMAL CONDITIONS. PLEASE SEE THE CODE |
| | SECTION WHICH WAS GIVEN ON PREVIOUS REVIEW WAS LS 101 |
| | 7.8 WHICH IS FOR MINIMUM LIGHTING LEVELS UNDER NORMAL |
| | CONDITIONS. THIS IS NOT FOR THE EMERGENCY (BATTERY BACK |
| | UP) LIGHT FIXTURE. |
| | PLEASE SEE THE LIGHTING LEVELS FOR EGRESS IN, AROUND |
| | AND EXITING BATHROOMS MAY NOT FALL BELOW 1FT CANDLE |
| | AVERAGE AT ALL EGRESS WALKING SURFACES. |
| | THIS COMMENT IS ALSO FOR OTHER EGRESS PATHS AS |
| | DESIGNATED AS GENERAL LIGHTING ON DIMMER PANEL MAY NOT |
| | FALL BELOW MINIMUM 1FT CANDLE LEVEL. PLEASE INDICATE |
| | HOW THIS IS BEING DONE. |
| | |
| | 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 14 WITH |
| | RESPECT TO LIGHTING CONTROLS REQUIRED IN SEPARATE |
| | SPACES AND AN EXAMPLE WAS NOTED *SUCH AS BATHROOMS*. |
| | THE RESPONSE MENTIONS THE PARTITIONS INSIDE THE |
| | BATHROOMS AND CONTROLS ARE NOT REQUIRED AS THESE |
| | PARTITIONS DO NOT GO ALL THE WAY TO THE CEILING. PLEASE |
| | SEE 13-415.1.ABC.1.1 AND .1.2. THE PREVIOUS COMMENT WAS |
| | NOT FOR THE STALL AREAS IN THE BATHROOMS. THIS WAS FOR |
| | THE *BATHROOMS* AS THEY ARE CONSIDERED SEPARATE SPACES |
| | FROM OTHER OPEN AREAS WITH LIGHTING CONTROLS. |
| | PLEASE SEE THIS AND ANY OTHER AREAS. |
| | PLEASE SEE THIS PREVIOUS REVIEW NOTE ALSO CONTAIN A |
| | NOTICE ABOUT THE OCCUPANT BEING ABLE TO VISUALLY SEE |
| | ALL LIGHTING IN WHICH IS BEING OVER RIDDEN. PLEASE SEE |
| | THE RESPONSE LETTER ONLY RESPONDED TO PARTITIONS IN |
| | BATHROOMS. PLEASE CLARIFY HOW THE OCCUPANT FROM EACH |
| | OVER RIDE/ ENTRANCE LOCATION CAN VISUALLY SEE THE |
| | LIGHTING WHICH IS BEING CONTROLLED OR MEETING THE |
| | EXCEPTION IN SAME SECTION AS PREVIOUSLY NOTED. THIS |
| | WOULD REQUIRE PILOT LIGHTS ETC CLEARLY LABELED. |
| | |
| | 5) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENT # 15 WITH |
| | RESPECT TO CHAPTER 13 AND ENERGY CALCULATIONS |
| | SUBMITTED. |
| | PLEASE KNOW THE PREVIOUS SUBMITTED METHOD WAS *A* WHICH |
| | IS NOW CHANGED TO METHOD *B* WHICH IS ACCEPTABLE |
| | HOWEVER PLEASE SEE FBC 13-400.3.B AS THE VERSION |
| | SUBMITTED IS NOT THE VERSION AS ADOPTED UNDER THE FBC. |
| | PLEASE SEE THE SECTION AS NOTED WHICH REFERENCES |
| | VERSION 2.5/400.B-04R. |
| | PLEASE SEE THE FOLLOWING SECTIONS TO THIS SAME NOTE: |
| | PLEASE SEE THE INPUT DATA REPORT WILL BE NOTED AS IDR |
| | ON THE FOLLOWING NOTES. |
| | |
| | A) ONCE AGAIN PLEASE CORRELATE ALL LIGHTING ON PLANS |
| | WITH THE IDR. PLEASE SEE SOME EXAMPLES WERE GIVEN ON |
| | PREVIOUS REVIEW HOWEVER THEY WERE NOT ALL. |
| | PLEASE SEE FOR EXAMPLE: THE EXTERIOR LIGHTING SHOWN ON |
| | PLANS DOES NOT COORDINATE WITH THE IDR FOR EXTERIOR |
| | LIGHTS. PLEASE SEE FIXTURES *H*, *BB*, *EM4*, ETC. |
| | PLEASE SEE FOR EXAMPLE: THE FIXTURES WHICH ARE NOTED AS |
| | INTERIOR LIGHTING WHEN THEY ARE LOCATED OUTSIDE. HOW IS |
| | THIS POSSIBLE? |
| | PLEASE SEE THE FIXTURES NOTED AS *EM4* ON PLANS ARE |
| | FIXTURES USED AS PART OF THE GENERAL LIGHTING WHICH ARE |
| | NOT EXEMPT. |
| | PLEASE ALSO SEE THE LIGHTING ON PLANS FOR INTERIOR |
| | FIXTURES DO NOT CORRELATE WITH THE IDR AND FIXTURE |
| | LEGEND. FOR EXAMPLE: SEE MISSING VA INPUTS FOR FIXTURES |
| | *P*, SEE MISSING VA REQUIRED FOR TRACK LIGHTING AS |
| | PREVIOUS NOTED, SEE ENTRY E1 FIXTURES AND COUNTS ON |
| | THESE IN HOST AREAS ETC |
| | |
| | THERE ARE SEVERAL INSTANCES ON PLANS AS NOTED WHICH |
| | NEED COORDINATION. PLEASE KNOW AS THE LOCATION |
| | DESIGNATIONS ON PLANS DO NOT CORRELATE WITH THE IDR AND |
| | BASED ON THE FACT NOT ALL LIGHTING IS FIGURED INTO THE |
| | IDR A COMPLETE REVIEW OF ALL ITEMS CAN NOT BE DONE AT |
| | THIS TIME.MECHANICAL ROOM, OTHER ROOM ON PLANS NEAR |
| | TOILET VESTIBULE NOT LABELED. |
| | PLEASE SEE 13-415.1.B, 13-415.2, 13-415.2.ABC.1.3, |
| | 13-415.2.ABC.1.2 (TRACK LIGHTING FOR LINE VOLTAGE AND |
| | LOW VOLTAGE) ETC. |
| | |
| | 6) NOTE: PLEASE SEE THE CERTIFICATION SHEET CONTAINS A |
| | SIGNATURE FOR THE PERSON WHO *PREPARED* CALCULATIONS |
| | HOWEVER DOES NOT LIST ANY INFORMATION FOR THIS PERSON. |
| | PLEASE LIST INFORMATION AS LICENSED PE IN THE STATE OF |
| | FLORIDA. PLEASE SEE 13-103.1, FAC 61G15-23.002, |
| | FS471.025. |
| | THE COVER SHEET CONTAINS SIGNATURES AND SEALS FROM TOW |
| | OTHER DESIGNERS HOWEVER THIS INFORMATION SHOULD BE ON |
| | THE CERTIFICATION SHEET AS STATED. |
| | |
| | 7) NOTE: PLEASE SEE PREVIOUS NOTE #12 WITH RESPECT TO |
| | LOADS FOR TRACK LIGHTING. PLEASE SEE RESPONSE MENTIONS |
| | LOAD WAS ADDED TO PANELS ON E4.1 HOWEVER COULD NOT |
| | LOCATE ON PLANS, PANELS OR ANY LOAD CALCULATIONS HOW |
| | THESE LOADS WERE DERIVED PER 220.43B. |
| | |
| | 8) NOTE: PLEASE SEE FIXTURES EM4 ON SOUTH SIDE OF ENTRY |
| | VESTIBULE WILL BE REQUIRED TO BE CIRCUITED TO THE LOCAL |
| | BRANCH CIRCUIT FEEDING OTHER *Q* FIXTURES IN THAT AREA |
| | PER 700.12F. |
| | PLEASE SEE THEY ARE CURRENTLY SHOWN COMING FROM SOUTH |
| | PATIO CIRCUIT. |
| | |
| | 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A |
| | NOTICE GIVEN AT THIS TIME. |
| | PLEASE KNOW ONE SET OF ELECTRICAL PLANS ALONG WITH ONE |
| | SET OF ENERGY CALCULATIONS ARE BEING RETAINED BY THIS |
| | OFFICE. |
| | |
| | |
| | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY |
| | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR |
| | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN |
| | CONTACTING THIS REVIEWER. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| 2008-01-29 20:16:33 | ON SET IN ELECTRICAL FOR REVIEW. |