| Date |
Text |
| 2007-10-01 09:52:11 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 FUEL GAS |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | MUNICIPAL CODES WPB |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ROUTE PLANS TO THE STATE OF FLORIDA, DEPT OF |
| | BUSINESS REGULATION, (DBPR), DIVISION OF HOTEL & |
| | RESTAURANT FOOD SERVICE LICENSE FOR REVIEW. REVIEWED |
| | SHEETS SHALL BE INSERTED INTO EACH SET OF PLANS AND THE |
| | TWO PAGE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED |
| | TO THE STAMPED PLANS REVIEWED BY DBPR. SECTION |
| | 102.2.1. |
| | |
| | 2. THE GREASE INTERCEPTOR SHALL BE INSPECTED AND SIZED |
| | BY THE UTILITY DEPT. INDUSTRIAL PRE-TREATMENT, |
| | ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO, |
| | (561) 822-2272, E-MAIL [email protected] OR CALVIN |
| | WILLIAMS (561) 822-2284, E-MAIL [email protected]. |
| | THEIR FAX NUMBER IS (561) 822-2287. A WRITTEN |
| | DETERMINATION SHEET FROM ENVIRONMENTAL COMPLIANCE SHALL |
| | BE SUBMITTED WITH THE PLANS SHOWING APPROVAL FOR |
| | EXISTING AND NEW GREASE INTERCEPTORS. WPB MUNICIPAL |
| | CODE ARTICLE III SECTION 90-124(7). |
| | |
| | 3. ALL ARCHITECTURAL SHEETS ARE MISSING REQUIRED |
| | INFORMATION. THE FIRM LICENSE NUMBER, (CERTIFICATE OF |
| | AUTHORIZATION), SIGNED, DATED SEAL, AND THE PRINTED |
| | NAME OF THE PERSON SEALING THE DOCUMENT IS REQUIRED IN |
| | THE TITLE BLOCK. ALSO THE SEAL APPEARS TO HAVE BEEN |
| | SIGNED WITH INITIALS. IF THIS IS INDEED THE LEGAL |
| | SIGNATURE OF THE ARCHITECT OF RECORD, THEN A SIGNED, |
| | SEALED, NOTORIZED LETTER SHALL BE SUBMITTED SHOWING THE |
| | LEGAL SIGNATURE OF THE ARCHITECT FOR OUR FILES. FAC |
| | 61G1-16.003, 61G1-16.004(2)(5)(6) & FS 481.219, |
| | 481.2055. |
| | |
| | 4. SHT A1.1 KEY NOTES WERE NOT FOUND. PLEASE CORRELATE |
| | KEY NOTES WITH FLOOR PLAN. SECTION 106.1.1. |
| | |
| | 5. SHT A8.1 DETAIL 9. SUBMIT MANUF SPECIFICATIONS FOR |
| | THE LAV DRAIN PAN. INDICATE REFERENCE STANDARD FOR LAV. |
| | SECTIONS 303, 303.1 303.2, & 303.4. |
| | |
| | 6. SHT A8.1 DETAIL 10 INDICATES A STORAGE CABINET WHERE |
| | THE LAV DRAIN PAN SHOULD BE PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 7. SHT FS-1 ITEM 86 WATER FILTER SYSTEM SHALL MEET THE |
| | REQUIREMENTS OF NSF-42. PLEASE SUBMIT MANUF. |
| | SPECIFICATIONS SHEETS SHOWING COMPLIANCE. SECTION |
| | 611.1. |
| | |
| | 8. SHTS FI-1 THRU FS-13 ARE SEALED BY THE ARCHITECT OF |
| | RECORD INDICATING "REVIEWED ONLY". IF THE PLANS ARE |
| | SIGNED AND SEALED THEN A TITLE BLOCK, PRINTED NAME OF |
| | THE PERSON SEALING THE DOCUMENT, DATED SEAL ETC IS |
| | REQUIRED. IF REVIEWING ONLY, INDICATE WITH A SHOP |
| | REVIEW APPROVAL STAMP ONLY SUCH AS USED IN SUBMITTALS. |
| | FAC 61G1-16.004 & FS 481.2055. |
| | |
| | 9. SHT FS-1 EQUIPMENT SCHEDULE ITEM #62 NOT FOUND ON |
| | THE FLOOR PLAN, & ITEM 147 INDICATES QTY 1 BUT 2 ARE |
| | SHOWN ON THE FLOOR PLAN. PLEASE CORRELATE. SECTION |
| | 106.1.1. |
| | |
| | 10. SHT FS-2 FOOD SERVICE EQUIPMENT SCHEDULE, ITEM 163 |
| | DOES NOT INDICATE DRAINAGE, AND ITEM 173 INDICATES |
| | DRAINAGE FOR A STORAGE CABINET. PLEASE CLARIFY. SECTION |
| | 106.1.1. |
| | |
| | 11. SHT FS-4 DETAILS INDICATED SUCH AS THE TRENCH DRAIN |
| | DETAIL, DRAIN SPECIFICATIONS, SECTION THRU FLOOR |
| | RECESS, INDIRECT WASTE & AIR GAP. WHERE THESE DESIGNED |
| | BY THE EQUIPMENT SUPPLIERS? PLEASE CLARIFY. SECTION |
| | 106.1. |
| | |
| | 12. ALL STRUCTURAL SHEETS. THE CERTIFICATE OF |
| | AUTHORIZATION NUMBER, PRINTED NAME OF THE ENGINEER, AND |
| | THE LICENSE NUMBER OF THE ENGINEER ARE REQUIRED ON THE |
| | TITLE BLOCK. ALSO THE PLANS APPEAR TO BE SIGNED WITH |
| | INITIALS. IF THIS IS INDEED THE LEGAL SIGNATURE OF THE |
| | ENGINEER, THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL |
| | BE SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR |
| | FILES. FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 13. ALL MEP SHEETS. THE CERTIFICATE OF AUTHORIZATION |
| | NUMBER, PRINTED NAME OF THE ENGINEER, AND THE LICENSE |
| | NUMBER OF THE ENGINEER ARE REQUIRED ON THE TITLE BLOCK. |
| | ALSO THE PLANS APPEAR TO BE SIGNED WITH INITIALS. IF |
| | THIS IS INDEED THE LEGAL SIGNATURE OF THE ENGINEER, |
| | THEN A SIGNED, SEALED, NOTORIZED LETTER SHALL BE |
| | SUBMITTED INDICATING THE LEGAL SIGNATURE FOR OUR FILES. |
| | FAC 61G15-23.002(2) & FS 471.025. |
| | |
| | 14. SHT P1.1 THE CONDENSATE FROM THE AHU'S SHALL NOT |
| | DRAIN INTO THE SANITARY SYSTEM. THE CONDENSATE SHALL |
| | DRAIN SEPARATELY OUT OF THE BUILDING AND CONNECT TO |
| | STORM DRAINAGE, A CATCH BASIN, A DRYWELL OR INTO A |
| | PLANTED AREA SO AS NOT TO CREATE A HAZARD. IF THE |
| | CONDENSATE CONNECTS TO THE STORM LINES OUTSIDE THE |
| | BUILDING, THEN A RELIEF VENT, (GOOSENECK), SHALL BE |
| | PROVIDED AS THE CONDENSATE LINE EXITS THE BUILDING. |
| | MUNICIPAL CODE ARTICLE III SECTION 90-125(5). |
| | |
| | 15. SHT P1.1 CONDENSATE FROM THE COOLER/FREEZER. FLOOR |
| | DRAINS ARE NOT APPROVED INDIRECT WASTE RECEPTORS. A |
| | FLOOR SINK OR HUB DRAIN IS REQUIRED. SECTIONS 802.3 & |
| | 802.3.2. |
| | |
| | 16. SHT P1.1 THE DISWASHER SHALL DRAIN TO THE SANITARY |
| | SYSTEM, NOT THE GREASE SYSTEM. MUNICIPAL CODE ARTICLE |
| | III SECTION 90-124(7)(B). PLEASE CHANGE THE FLOOR PLAN |
| | AND THE SANITARY RISER DIAGRAM. |
| | |
| | 17. SHT P1.1 PLUMBING WASTE & VENT PLAN NOTES #6. |
| | CLEANOUTS TO BE PROVIDED AT THE BASE OF THE STACK PER |
| | SECTION 708.3.4. PLEASE INDICATE THE CORRECT LOCATION |
| | FOR THE CLEANOUTS. |
| | |
| | 18. SHT P1.1 VBF'S DO NOT MEET THE REQUIREMENTS OF |
| | SECTION 913, ISLAND VENTS. (SEE ATTACHED SHEET FOR |
| | REQUIRED PIPING). PLEASE CORRECT VENTING TO COMPLY WITH |
| | SECTION 913. |
| | |
| | 19. SHT P2.1 THE 3" GAS LINE IS INDICATED AS HAVING |
| | 1,812 CFH & 1,482 CFH ON THE SAME LINE DOWNSTREAM OF |
| | THE METER. PLEASE ONLY SHOW THE CORRECT LOAD ON THE GAS |
| | LINE. SECTION 106.1.1. |
| | |
| | 20. SHT P2.1 PLUMBING PLAN NOTES #3. THE RPZV BACKFLOWS |
| | SHALL BE INSTALLED A MAXIMUM 4' ABOVE THE FLOOR FOR |
| | CERTIFICTION AND SERVICE. PLEASE INDICATE ON PLANS. |
| | SECTION 106.2.1. |
| | |
| | 21. SHT P2.1 PLUMBING PLAN NOTES #11 THE GAS PROVIDER |
| | SUPPLIES THE GAS AT EITHER 2 PSI OR 1/2 PSI, (12" TO |
| | 14" W.C.). PLANS INDICATE 7" W.C. PLEASE CONTACT THE |
| | GAS PROVIDER AND INDICATE THE INLET PRESSURE PROVIDED. |
| | SECTION 402. |
| | |
| | 22. SHT P3.1 A SEPARATE GAS PERMIT IS REQUIRED. THE |
| | FOLLOWING INFORMATION IS REQUIRED: |
| | |
| | A. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. - THE LENGTHS OF PIPE ARE NOT |
| | INDICATED. |
| | |
| | B. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE IF BEING USED. |
| | |
| | C. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). - TO BE VERIFIED ONCE |
| | REQUIREMENT "A" IS ADDRESSED. |
| | |
| | D. SUBMIT CALCULATIONS FOR COMBUSTION |
| | AIR (IF APPLICABLE) PER FBC-2004 FUEL |
| | GAS CODE SECTION 304. |
| | |
| | E. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. - SEE COMMENT |
| | #21. |
| | |
| | F. SUBMIT A DETAIL SHOWING THE TYPE, |
| | LOCATION, SIZE AND TERMINATION OF THE |
| | GAS VENTS PER FBC-2004 FUEL GAS CODE |
| | SECS. 502 THRU 505. |
| | |
| | G. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| | EQUIPMENT TO VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2.--NO MANUF. SHEETS |
| | FOR ITEM #5RICE COOKERS, THE WATER HEATERS, AND THE |
| | RH UNITS. |
| | |
| | H. EMERGENCY HOOD SHUT DOWN SHUT OFF |
| | VALVE TO BE BELOW CEILING. MANUAL SHUT |
| | OFF VALVE TO BE UPSTREAM. UNION TO BE |
| | DOWN STREAM OF MANUAL VALVE. - UNION NOT SHOWN. |
| | |
| | 23. SHT P3.1 GAS RISER DIAGRAM, 2-1/2" REQUIRED FOR |
| | 1078 CFH, 1-1/4" REQUIRED TO EACH WATER HEATER, 2" |
| | REQUIRED FOR 374 CFH TO 1ST RH, 1" REQUIRED FOR THE |
| | RICE COOKERS (2) & 1-1/2" REQUIRED TO THE FRYERS. TABLE |
| | 402.4(2) - (IF SCHEDULE 40 PIPE). |
| | |
| | 24. SHT P3.2 GREASE WASTE RISER DIAGRAM DOES NOT |
| | REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. THE ISLAND VENTS SHALL CONNECT TO THE |
| | DRAIN AT THE LOWEST POINT, AND CLEANOUTS ARE REQUIRED |
| | ON BOTH VENT LINES. (SEE ATTACHED SHEET). |
| | |
| | 25. SHT P3.2 GREASE WASTE & VENT RISER VENT DOES NOT |
| | MEET CODE PER SECTION 905.4. VENTS ARE TURNING |
| | HORIZONTALLY PRIOR TO 6" ABOVE THE FLOOD RIM LEVEL OF |
| | THE FLOOR SINKS. (SEE GENERAL NOTE). |
| | |
| | 26. SHT P3.2 GREASE WASTE & VENT RISER DOES NOT REFLECT |
| | THE FLOOR PLAN. FLOOR SINK (107) IS NOT SHOWN ON THE |
| | FLOOR PLAN.--IDENTIFY THE FIXTURE THAT THE ICE |
| | MACHINE IS DRAINING INTO. AN INDIRECT WASTE RECEPTOR IS |
| | REQUIRED. SECTIONS 106.1.1, 802.3 & 802.3.2. |
| | |
| | 27. SHT P3.2 SANITARY WASTE & VENT RISER DIAGRAM DOES |
| | NOT REFLECT THE FLOOR PLAN, NOR DOES IT MEET CODE |
| | REQUIREMENTS. 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR |
| | PLAN THAT ARE NOT ON THE RISER DIAGRAM.--PIPING TO |
| | FIXTURE 166 DOES NOT REFLECT THE FLOOR PLAN.-- PIPING |
| | UPSTREAM OF FIXTURE 162 DOES NOT RELFECT THE FLOOR |
| | PLAN. (AS SHOWN ON THE FLOOR PLAN IT IS A DRY |
| | HORIZONTAL VENT WHICH IS NOT APPROVED PER SECTION 905.3 |
| | & SECTION 905.4.--THE ISLAND VENT FOR FIXTURE 166 |
| | DOES NOT MEET CODE REQUIREMENT. (SEE ATTACHED SHEET). |
| | |
| | 28. SHT P3.3 SHOW WATER HAMMER ARRESTORS REQUIRED BY |
| | SECTION 604.9 ON THE RISER DIAGRAM. (QUICK CLOSING |
| | VALVES SUCH AS WASHING MACHINE, ICE MAKER ETC.). THE |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED NEAR THE |
| | FIXTURES IN AN "EFFECTIVE RANGE" NO IN THE CEILING. |
| | PDI-WH 201 AND MANUF. INSTALLATION INSTRUCTIONS. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |