| 2007-10-04 14:29:10 | *****DENIED***** |
| | |
| | |
| | 01.THE SUITE NUMBER SHALL BE INCLUDED WITH THE |
| | PROJECT SITE ADDRESS LOCATED IN THE TITLE BLOCK OF EACH |
| | SUBMITTED PLAN SHEET. |
| | |
| | 02.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE |
| | REFERENCED.ADD TO CODE ANALYSIS UNDER APPLICABLE |
| | CODES (SHEET T1.1). |
| | |
| | 03.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR |
| | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. |
| | |
| | 04.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY |
| | AS NECESSARY FOR SAFE OPERATION. |
| | |
| | 05.ON THE APPROPIATE EXTERIOR ELEVATION WHICH FRONTS |
| | SOUTH ROSEMARY AVENUE, DISPLAY THE SUITE NUMBER.AS |
| | PER WEST PALM BEACH CODE, TENANT SPACE NUMBERS SHALL BE |
| | NO LESS THA 3" IN HEIGHT AND NO LESS THAN 1" IN WIDTH. |
| | |
| | 06.PLEASE PROVIDE FLAME SPREAD DETAILS FOR THE ENTRY |
| | CANOPY. |
| | |
| | 07.A DOOR NORMALLY REQUIRED TO BE KEPT CLOSED SHALL |
| | BE SELF-CLOSING OR AUTOMATIC CLOSING IN ACCORDANCE WITH |
| | 7.2.1.8.2 OF NFPA 101. |
| | |
| | 08.COMMERCIAL COOKING EQUIPMENT SHALL BE IN |
| | ACCORDANCE WITH NFPA 96.SEPARATE PLANS AND PERMIT |
| | WILL BE REQUIRED FOR THE HOOD INSTALLATION AS WELL AS |
| | THE HOOD SUPPRESSION SYSTEM. |
| | |
| | 09.SPECIFY INTERIOR FINISH CLASSIFICATION FOR THE |
| | WALLS AND CEILINGS.INTERIOR WALL AND CEILING FINISH |
| | MATERIALS SHALL BE CLASS A OR CLASS B IN GENERAL |
| | ASSEMBLY AREA HAVING AN OCCUPANT LOAD S OF MORE THAN |
| | 300. |
| | |
| | 10.SPECIFY THE INTERIOR FLOOR FINISH IN TERMS OF |
| | CLASS I OR CLASSII. |
| | |
| | 11.THE 2002 EDITION NFPA 13 SHALL BE BE REFERENCED |
| | FOR THE FIRE SPRINKLER INSTALLATION AND/RE-MODEL. |
| | |
| | 12.THE 2002 EDITION OF NFPA 72 SHALL BE REFERENCED |
| | FOR THE INSTALLATION/RE-MODEL OF THE FIRE ALARM |
| | SYSTEM. |
| | |
| | 13.AS PER LOCAL REQUIREMENTS, DUCT SMOKE DETECTORS |
| | SHALL INITIATE A GENERAL FIRE ALARM.AMEND FIRE ALARM |
| | GENERAL NOTE 6 ON SHEET F1.1 AND ALSO THE FIRE ALARM |
| | SEQUENCE OF OPERATIONS ON SHEET F2.1 SECTION 16C 2-3. |
| | |
| | |
| | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE |
| | LETTER INDICATING WHERE (ON THE PLAN OR IN THE |
| | SPECIFICATIONS) EACH COMMENT WAS ADDRESSED |
| | |
| | CAPT. MICHAEL A. WILLIAMS |
| | FIRE PLAN REVIEW |
| | 561-805-6722 |